Where it goes and how it fits
The 45 mm width fits into a standard control panel.
Real-world deployment notes
Rated for operation from -5 °C to 55 °C ambient, with storage from -60 °C to 80 °C — fine for most indoor industrial environments, but if this lives in an unheated warehouse in a cold climate, the -5 °C lower operating limit matters; the contactor won't pull in reliably below that. It derates above 3000 m altitude, so at a high-altitude mine or mountain site, you need to check the thermal curve. The non-overlap time of 1.5 ms between NC and NO contacts is built in — that's a safety feature for interlocking, ensuring the NC opens before the NO closes on energisation and vice versa on de-energisation. That's good for reversing starters or bypass circuits where you can't have both sets closed simultaneously.