Skip to main content
Schneider Electric LC1E200PCH2S260N — Contactors

Schneider LC1E200PCH2S260N Easy TeSys PWM Contactor 200A 12-32V DC | aoctrl

MPNLC1E200PCH2S260N
Active

Schneider Electric Easy TeSys Control LC1E200PCH2S260N contactor, 1-pole, 200 A resistive load, 1000 V DC maximum switching voltage, 12-32 V DC coil, IP60.

$400.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E200PCH2S260N — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E200PCH2S260N — Contacts & Poles
ParameterValue
Pole configuration1P
LC1E200PCH2S260N — Environmental
ParameterValue
IP degree of protectionIP60
Operating altitude13123.36 ft (4000 m) without derating
Mechanical robustnessVibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)
LC1E200PCH2S260N — Approvals
ParameterValue
StandardsIEC 60947-4-1 GB/T 14048.4
LC1E200PCH2S260N — Mechanical
ParameterValue
Width2.6 in (66.5 mm)
Height2.9 in (74.3 mm)
Depth3.2 in (81.3 mm)

Product details

Active production, DC-rated switching

The LC1E200PCH2S260N is a current-production Easy TeSys Control contactor from Schneider Electric, rated for 200 A continuous on resistive loads with a maximum switching voltage of 1000 V DC. The control circuit runs on 12...32 V DC, pulling 28 W inrush and 2.4 W hold-in — the wide dropout range (0.1...0.75 Uc) means it drops out cleanly even on a sagging battery bus.

DC switching limits and short-time ratings

This is a 1-pole contactor with 1 NO main contact, designed for DC switching. The 1000 V DC maximum switching voltage and 1500 V rated insulation voltage (IEC 60947-4-1) mean it handles high-voltage DC bus work — solar combiner boxes, battery banks, or DC motor fields. Short-time ratings let it ride through surges: 250 A for 15 minutes, 320 A for 5 minutes, 600 A for 30 seconds, and 900 A for 10 seconds. That's useful for capacitor pre-charge or inrush from a DC bus with high capacitance. Minimum switching is 0.1 A at 8 V DC — below that the contacts may not wet cleanly, so don't use it for dry-circuit signal switching.

Panel fit and environmental specs

The contactor measures 2.6 in wide by 2.9 in tall by 3.2 in deep (66.5 x 74.3 x 81.3 mm), with vertical mounting support. Power circuit terminals use M8 bolts with flat and spring washers, torqued to 70.8...88.5 lbf·in (8...10 N·m). Operating temperature spans -40...185 °F (-40...85 °C), and it runs at altitudes up to 4000 m without derating. Mechanical durability is 300,000 cycles; electrical durability on the 200 A resistive load at 750 V DC is 1500 cycles for breaking-only duty (0.6 s closed, 5.4 s open). At 1000 V DC, that drops to 1000 cycles.

Frequently asked questions

What is the LC1E200PCH2S260N used for?

It is a 1-pole DC contactor rated for 200 A resistive loads with a maximum switching voltage of 1000 V DC. Typical applications include DC bus switching in solar combiner boxes, battery banks, and DC motor control circuits.

MPN
LC1E200PCH2S260N