Skip to main content
Schneider Electric LC1E25004B7IN — Contactors

Schneider LC1E25004B7IN Easy TeSys Contactor, 4P 50A AC-1 24

MPNLC1E25004B7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E25004B7IN, 4P(4NO) contactor, AC-1 ≤415 V 50 A, 24 V coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E25004B7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E25004B7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E25004B7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E25004B7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E25004B7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E25004B7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

The LC1E25004B7IN is a 4-pole (4NO) contactor from Schneider Electric's Easy TeSys Control range, rated 50 A in AC-1 utilisation category at ≤415 V with a 24 V coil. AC-1 means it's designed for resistive loads — heaters, lighting banks, non-inductive elements — not motor starting. The 4 NO poles give you four independent switching paths, useful for multi-circuit resistive banks or as a main contactor in a resistive load panel.

Sourcing reality — this part is obsolete

Schneider has marked the LC1E25004B7IN as obsolete. No official successor order code is listed, so the replacement path is not a simple cross-reference.

Physical fit and integration

The contactor measures 56 mm wide by 64 mm high by 93 mm deep, and mounts on either a plate or a DIN rail. At 93 mm depth, it projects further from the rail than a typical compact contactor — factor that into enclosure depth and gland-plate clearance. IP2X protection means the housing is finger-safe but not sealed against dust or moisture; keep it inside an IP54 or better enclosure in any industrial environment. The protective treatment is TH (pollution degree 3) per IEC 60068, so it handles the conductive-dust conditions common in light-industrial panels.

Standards and compliance footprint

Fire resistance is rated to 850 °C per IEC 60695-2-1, so it meets the glow-wire test for unattended equipment. Operating altitude is 3000 m, which covers most high-altitude installations without derating.

Frequently asked questions

What replaces the LC1E25004B7IN?

No official successor order code is listed. The replacement is not a direct cross-reference — you will need to evaluate a form-fit-function alternative from the current Easy TeSys or TeSys Deca range, or source the original code through surplus channels.

What are the key ratings for this contactor?

4 poles (4NO), AC-1 utilisation category, rated operational voltage ≤415 V, rated current 50 A, coil voltage 24 V. It is designed for resistive loads, not motor starting.

What compliance documentation is available?

The contactor is certified to EN/IEC 60947-1, -4-1, and -5-1, plus Chinese GB/T 14048.1, -4, and -5. Fire resistance is tested to 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068.

MPN
LC1E25004B7IN