Skip to main content
Schneider Electric LC1E25004E7IN — Contactors

Schneider LC1E25004E7IN Easy TeSys Contactor, 4P, AC-1 50A,

MPNLC1E25004E7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E, 4P(4NO), AC-1 ≤415V 50A, 48V coil, obsolete lifecycle.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E25004E7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E25004E7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E25004E7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E25004E7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E25004E7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E25004E7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

It is rated for 50 A at ≤415 V, with a 48 V coil.

The AC-1 rating of 50 A at ≤415 V governs resistive loads — heaters, incandescent lighting, or resistive banks. That is not a motor-switching rating; for inductive motor loads (AC-3), this contactor would derate significantly. The 48 V coil is a control-circuit voltage, common in older panel designs or low-voltage control schemes. The 4P (4NO) configuration gives four normally-open power poles, which suits single-phase or three-phase resistive circuits where all poles switch simultaneously. Operating altitude is 3000 m, and the protective treatment is TH (pollution degree 3) per IEC 60068 (cite:,).

Mechanical and environmental robustness

The contactor is rated for vibration: 1.5 Gn (5–300 Hz) when open, 3 Gn when closed. Shock ratings: 10 Gn for 11 ms when closed, 6 Gn for 11 ms when open (cite:). These figures mean it holds its contacts under moderate industrial vibration — suitable for panel-mounted use near pumps or conveyors, but not extreme high-G environments.

Frequently asked questions

What is the closest alternative to the LC1E25004E7IN?

No official successor order code is recorded in the lifecycle data. A qualified cross-reference search within the Easy TeSys Control range is needed — the closest functional match would be a 4P contactor with the same AC-1 current rating and coil voltage, but pin compatibility and footprint must be verified against the specific panel layout.

What are the key ratings of the LC1E25004E7IN?

4-pole (4NO) contactor, AC-1 utilisation category, rated 50 A at ≤415 V, with a 48 V coil. Mounts on plate or DIN rail. IP2X protection. Complies with EN/IEC 60947-1, -4-1, -5-1.

MPN
LC1E25004E7IN