Skip to main content
Schneider Electric LC1E25004M7IN — Contactors

Schneider LC1E25004M7IN Easy TeSys Contactor, 4P, AC-1 50A

MPNLC1E25004M7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E25004M7IN, 4P(4NO) contactor, AC-1 ≤415V 50A, 220V coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E25004M7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E25004M7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E25004M7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E25004M7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E25004M7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E25004M7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

The LC1E25004M7IN is a 4-pole contactor from Schneider Electric's Easy TeSys Control range, designed for resistive load switching under AC-1 utilisation category. It's rated for 50 A at up to 415 V, making it a fit for heater banks, lighting circuits, or other non-inductive loads in a control panel. Mounts on DIN rail or a backplate, with a compact footprint of 56 mm wide by 64 mm tall by 93 mm deep — sized for a standard enclosure without crowding adjacent devices. The IP2X finger-protection rating means the contactor's live parts are shielded against accidental contact during panel access, which is the minimum expected for enclosed industrial gear.

The AC-1 utilisation category is the key spec here: it governs resistive loads where inrush is minimal. At 50 A and 415 V, this contactor handles steady-state heater or resistor bank current without the derating needed for motor (AC-3) duty. If your application is inductive — motors, transformers — this part is not the right choice; you'd need an AC-3 or AC-4 rated contactor instead. Compliance with EN/IEC 60947-4-1 (contactors and motor-starters) and GB/T 14048.4 (Chinese national standard) covers most industrial installations globally, including CE-marked panels and projects requiring Chinese CCC certification.

Frequently asked questions

What replaces the LC1E25004M7IN?

No official successor order code is listed in the available records. A replacement would need to be selected based on the original AC-1 rating (50 A at 415 V) and coil voltage (220 V) from the current Easy TeSys or TeSys Deca range, but pin-compatibility and footprint should be verified.

What are the key ratings of this contactor?

It is a 4-pole (4NO) contactor rated for AC-1 resistive loads at 50 A, up to 415 V, with a 220 V coil. It mounts on DIN rail or plate and measures 56 x 64 x 93 mm.

What standards does the LC1E25004M7IN comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese equivalents GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5. It also has 850 °C glow-wire fire resistance per IEC 60695-2-1.

MPN
LC1E25004M7IN