Skip to main content
Schneider Electric LC1E25008M7IN — Contactors

Schneider Electric LC1E25008M7IN Easy TeSys Contactor, 4P, 5

MPNLC1E25008M7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E25008M7IN, 4P (2NO+2NC) contactor, AC-1 50A at ≤415V, 220V coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E25008M7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E25008M7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E25008M7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E25008M7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E25008M7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E25008M7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

It's rated for AC-1 utilisation category at 50 A up to 415 V with a 220 V coil, meaning it's designed for resistive loads like heaters or lighting banks where the switching current and load current are essentially the same — no motor inrush to worry about. It mounts to either a plate or DIN rail, takes up 56 mm width on the rail, and carries IP2X finger protection on the enclosure. The operating temperature range is -5 to 55 °C, with storage from -60 to 80 °C, and it's rated for use up to 3000 m altitude.

This part is marked obsolete by the manufacturer. No official successor order code exists. We can source it against an RFQ from surplus or broker channels.

The contactor also meets IEC 60695-2-1 for glow-wire fire resistance at 850 °C and carries protective treatment TH (pollution degree 3) per IEC 60068 for use in mildly corrosive or humid environments.

Mechanical and Environmental Robustness

Rated for vibration at 1.5 Gn (5–300 Hz) when open and 3 Gn when closed, and shock at 6 Gn open / 10 Gn closed — figures that matter if this contactor lives on a machine with frequent start/stop jolts or near a press.

Frequently asked questions

What are the key ratings I need to check for fit?

The critical numbers are: 4-pole configuration (2NO+2NC), AC-1 utilisation category at 50 A up to 415 V, and a 220 V coil. That means it's for resistive loads only — not for motor starting where AC-3 rating would be needed. Mounting is plate or DIN rail, 56 mm wide.

What compliance documentation is available?

The contactor carries certifications to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and GB/T equivalents. It also meets IEC 60695-2-1 glow-wire at 850 °C and IEC 60068 protective treatment TH (pollution degree 3).

MPN