Specifications

LC1E25008N5WB — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E25008N5WB — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E25008N5WB — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E25008N5WB — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E25008N5WB — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E25008N5WB — Mechanical
ParameterValue
Width56 mm
Height84 mm
Depth93 mm

Product details

The Schneider Electric LC1E25008N5WB is a 4-pole contactor from the Easy TeSys Control range, rated for 40 A in AC-1 utilisation category at up to 440 V AC. That AC-1 rating means it's specified for resistive loads — heaters, ovens, lighting banks — where the switching arc is less aggressive than motor starting. The 415 V AC 50 Hz control coil is a wide-range design, holding in from 0.7 to 1.25 Uc and dropping out between 0.3 and 0.6 Uc across the -5 to 55 °C operating band. The 4-pole configuration is 2 NO + 2 NC, giving flexibility for two-circuit switching without an auxiliary block.

Mounts on either a plate or standard DIN rail — the 56 mm width and 84 mm height fit a standard 4-module footprint on a 35 mm rail. Screw-clamp terminals accept up to 6 mm² on the power circuit and 4 mm² on the control circuit, with a tightening torque of 1.5 N·m and 1.2 N·m respectively. The IP20 finger-safe enclosure is standard for panel-mount contactors; no additional shrouding needed inside a closed cabinet.

The TH protective treatment per IEC 60068-2-30 means it's tested for humid tropical environments — relevant if the panel sees condensation or high relative humidity.

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current is 40 A in AC-1 (resistive load) at up to 440 V AC. The control coil is 415 V AC 50 Hz. Rated insulation voltage is 690 V. Breaking capacity is 200 A at 440 V, and making capacity is 250 A at 440 V.

What compliance documentation is available for this part?

The contactor is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, and EN/IEC 60947-5-1, plus the Chinese GB/T 14048 series. It carries TH protective treatment per IEC 60068-2-30 and fire resistance to 850 °C per IEC 60695-2-1.