Skip to main content
Schneider Electric LC1E250ADCH2S260N — Contactors

Schneider LC1E250ADCH2S260N Contactor, 1P DC 12V 250A

MPNLC1E250ADCH2S260N
Active

Schneider Electric Easy TeSys LC1E250ADCH2S260N DC contactor, 1-pole, 12 V DC coil, 250 A resistive, 1000 V DC max switching.

$24.01Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E250ADCH2S260N — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E250ADCH2S260N — Contacts & Poles
ParameterValue
Pole configuration1P
LC1E250ADCH2S260N — Environmental
ParameterValue
IP degree of protectionIP60
Operating altitude13123.36 ft (4000 m) without derating
Mechanical robustnessVibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)
LC1E250ADCH2S260N — Approvals
ParameterValue
StandardsIEC 60947-4-1 GB/T 14048.4
LC1E250ADCH2S260N — Mechanical
ParameterValue
Width2.3 in (58 mm)
Height2.9 in (74.3 mm)
Depth3.2 in (81.3 mm)

Product details

The Schneider LC1E250ADCH2S260N is a 1-pole DC contactor from the Easy TeSys range, rated for 250 A continuous resistive loads (Ith) at up to 1000 V DC switching. The 12 V DC coil holds at 0.85–1.1 Uc (operational) and drops out between 0.1–0.75 Uc, so a 12 V supply with proper tolerance keeps it pulled in without dropout. Application is explicitly resistive load. Do not use this for motor starting or inductive loads – the electrical durability figures (1500 cycles at 750 V / 250 A breaking only) confirm it's built for on/off of resistors, heaters, or lamps, not for making/breaking motor inrush. Mechanical durability is 300,000 cycles, and close/open times are 50 ms / 30 ms. That kind of speed and endurance suits a heater bank cycling on a packaging line or a resistive load switched at moderate frequency.

Mounts vertically on a panel (vertical support). Dimensions: 74.3 mm high, 58 mm wide, 81.3 mm deep. Power terminals take M8 bolts with flat and spring washers, torqued to 8–10 N·m. Control circuit comes with a 40 cm two-wire pigtail. IP60 rating means it's dust-tight but not protected against sprays or hoses. Keep it outside washdown zones unless it's inside a panel rated higher.

Designed to IEC 60947-4-1 and GB/T 14048.4. Rated insulation voltage 1500 V (power circuit), impulse withstand 8 kV (coil not connected to power circuit). Insulation resistance is 1000 MΩ at 1000 V DC.

Sourcing Takeaway

For a BOM line needing a 1-pole, 12 V DC coil contactor switching 250 A resistive at up to 1000 V DC, the LC1E250ADCH2S260N is a direct fit. No obsolete hunt needed – it's in active manufacture, so lead times are normal production. Submit an RFQ to confirm current pricing and availability.

Frequently asked questions

What are the key electrical ratings?

Conventional free air thermal current (Ith) 250 A for the power circuit, control circuit voltage 12 V DC, maximum switching voltage 1000 V DC, minimum switching current 0.1 A at 8 V DC.

What compliance standards does it meet?

It complies with IEC 60947-4-1 and GB/T 14048.4. Rated insulation voltage 1500 V, impulse withstand 8 kV (coil not connected to power circuit).

MPN
LC1E250ADCH2S260N