Skip to main content
Schneider Electric LC1E250ASCH2S260N — Contactors

Schneider LC1E250ASCH2S260N Easy TeSys Contactor, 1P, 250A, 12V DC

MPNLC1E250ASCH2S260N
Active

Schneider Electric, Easy TeSys, Contactor, LC1E250ASCH2S260N, 250 A, 1000 V DC, 1 NO, 12 V DC coil, vertical mount, M8 terminals, IP60, -40…85 °C.

$24.01Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E250ASCH2S260N — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E250ASCH2S260N — Contacts & Poles
ParameterValue
Pole configuration1P
LC1E250ASCH2S260N — Environmental
ParameterValue
IP degree of protectionIP60
Operating altitude13123.36 ft (4000 m) without derating
Mechanical robustnessVibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)
LC1E250ASCH2S260N — Approvals
ParameterValue
StandardsIEC 60947-4-1 GB/T 14048.4
LC1E250ASCH2S260N — Mechanical
ParameterValue
Width2.6 in (66.5 mm)
Height2.9 in (74.3 mm)
Depth3.2 in (81.3 mm)

Product details

Certified DC Contactor for Resistive Loads

The LC1E250ASCH2S260N is a single-pole, normally open contactor from the Easy TeSys range, designed for DC resistive load switching up to 250 A continuous. It complies with IEC 60947-4-1 and GB/T 14048.4, making it a drop-in replacement for CE-marked panels and global installations. Rated for 1000 V DC maximum switching voltage and a control circuit of 12 V DC, this contactor is well-suited for battery disconnect, DC power distribution, and resistive heating applications where one-line interruption is acceptable.

Mounting and Connection Details

Mounting support specifies vertical orientation only — do not mount horizontally. The power circuit uses M8 bolt terminals with flat and spring washers, requiring a tightening torque of 70.8…88.5 lbf·in (8…10 N·m). Control circuit comes with a 2-wire, 40 cm fly lead. Operating altitude is 4000 m without derating, and ambient air temperature range is -40…85 °C for both operation and storage. IP60 protection keeps out dust but not water — install in a suitable enclosure.

Electrical Performance and Lifecycle

Closing time is 30 ms; opening is 15 ms. Control circuit picks up at 0.85–1.1 Uc (12 V DC) and drops out at 0.1–0.75 Uc. Average impedance is 0.5 mOhm at 250 A.

Short-Time Ratings and Thermal Considerations

The contactor can carry 250 A continuously; higher currents are permitted for limited durations: 375 A for 10 min, 500 A for 5 min, 1000 A for 20 s, and 2000 A for 0.3 s. These short-time ratings help coordinate with upstream protective devices. Inrush power is 32 W; hold-in power is 3.5 W.

Frequently asked questions

Is the LC1E250ASCH2S260N compliant with IEC 60947-4-1 and GB/T 14048.4?

Yes, the contactor meets both IEC 60947-4-1 and GB/T 14048.4 standards for power circuit switching. It is suitable for replacement in CE-marked panels.

Can this contactor be mounted horizontally?

No, the mounting support specifies vertical orientation only. Horizontal mounting is not supported and may affect performance or reliability.

What are the closing and opening times?

Closing time is 30 ms; opening time is 15 ms. These fast switching speeds allow synchronization with conveyor interlocks and other time-critical sequences.

What type of terminals does this contactor use?

The power circuit uses M8 bolt terminals with flat and spring washers. The control circuit comes with a 2-wire, 40 cm fly lead. Tighten power connections to 70.8…88.5 lbf·in (8…10 N·m).

Is this contactor suitable for single-phase motor control?

With only one NO pole, it switches one line. For single-phase motors, local codes typically require disconnecting both live and neutral, which a single-pole contactor cannot provide. It is better suited for DC resistive loads or applications where single-pole interruption is acceptable.

MPN
LC1E250ASCH2S260N