Mounting and termination
The LC1E300ASCH2S260N: Mounts vertically; power connections M8 bolts torqued to 8–10 Nm (70.8–88.5 lbf·in); control circuit 40 cm two-wire fly lead with one NO auxiliary. Permissible short-time: 400 A 10 min, 600 A 5 min, 1000 A 30 s.
Field notes on the coil
Inrush power is 32 W, holding at 3.5 W DC. Dropout threshold is 0.75 Uc, which can act as a low-voltage release.