It is rated for AC-1 utilisation category at 16 A on a power circuit up to 415 V, with a 110 V AC coil. That AC-1 rating means it is specified for resistive loads — heaters, lighting banks, or other non-inductive circuits — where the switching current and the load current are essentially the same. The contactor carries EN/IEC 60947-4-1 and GB/T 14048.4 approvals, so it meets the standard for contactors and motor-starters across European and Chinese installations.
Mounts on a plate or DIN rail (35 mm symmetrical rail per EN 60715). The footprint is 56 mm wide by 64 mm tall by 93 mm deep — a compact 4-pole block that fits standard 4-module spacing on the rail. IP2X finger protection on the front means it is safe for open-panel mounting where operators might brush against the enclosure, but it is not sealed against dust or moisture. The TH protective treatment (pollution degree 3) per IEC 60068 means it tolerates conductive pollution in industrial atmospheres — typical for a panel-mounted contactor in a factory environment.