Schneider Electric LC1E32004V7IN — Contactors

Schneider Electric LC1E32004V7IN Easy TeSys Contactor, 4P, 5

MPNLC1E32004V7IN
Obsolete

Schneider Electric Easy TeSys Control, contactor, LC1E32004V7IN, 4P (4NO), AC-1 ≤415V 55A, 400V coil.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E32004V7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load

Ratings & Performance

LC1E32004V7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1

Contacts & Poles

LC1E32004V7IN — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LC1E32004V7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E32004V7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E32004V7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

The Schneider Electric LC1E32004V7IN is a 4-pole contactor from the Easy TeSys Control range, rated for AC-1 utilisation category at 55 A on power circuits up to 415 V. AC-1 covers resistive loads — heaters, lighting banks, non-inductive elements — where the switching current and load current are essentially the same. The 4 NO (normally open) pole configuration gives you four independently switched power paths in a single 56 mm wide package that mounts on DIN rail or a plate.

The headline 55 A at ≤415 V in AC-1 is the thermal current rating for resistive loads — this contactor can carry and break that current continuously under those conditions. The 4-pole arrangement means each NO pole shares the load; for a balanced three-phase resistive heater plus neutral, you'd use three poles for the phases and one for the neutral, staying within the 55 A per-pole limit.

At 56 mm wide, 64 mm tall, and 93 mm deep, this contactor fits standard DIN-rail enclosures or can be plate-mounted. The IP2X finger protection means the live terminals are shielded against accidental contact — enough for a general-purpose control cabinet but not for washdown areas. Operating ambient is -5 to 55 °C, with storage from -60 to 80 °C; the TH protective treatment (pollution degree 3 per IEC 60068) means it handles the dusty, humid conditions common in industrial panels without conformal coating.

Frequently asked questions

What are the key ratings of the LC1E32004V7IN?

It is a 4-pole (4 NO) contactor rated 55 A in AC-1 utilisation category at ≤415 V, with a 400 V coil. It mounts on DIN rail or a plate, measures 56 x 64 x 93 mm, and carries certifications to EN/IEC 60947-1, -4-1, -5-1 and GB/T equivalents.

What compliance documentation is available for this contactor?

The contactor is certified to EN/IEC 60947-1 (general rules), EN/IEC 60947-4-1 (contactors and motor-starters), EN/IEC 60947-5-1 (control circuit devices), and the Chinese GB/T 14048.1, 14048.4, 14048.5 equivalents. It also meets IEC 60695-2-1 for glow-wire fire resistance at 850 °C and has TH protective treatment per IEC 60068 for pollution degree 3.

MPN
LC1E32004V7IN