Skip to main content
Schneider Electric LC1E32008M7IN — Contactors

Schneider LC1E32008M7IN Easy TeSys Contactor, 55A AC-1, 4P,

MPNLC1E32008M7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E32008M7IN, 4P (2NO+2NC) contactor, AC-1 ≤415V 55A, 220V coil, obsolete.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E32008M7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load

Ratings & Performance

LC1E32008M7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1

Contacts & Poles

LC1E32008M7IN — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LC1E32008M7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E32008M7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E32008M7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

The Schneider Electric LC1E32008M7IN is a 4-pole contactor from the Easy TeSys Control range, rated AC-1 at 55 A up to 415 V with a 220 V coil.

The AC-1 utilisation category means this contactor is rated for switching resistive loads — heaters, ovens, lighting — where the current inrush is low and the power factor is near unity. At 55 A on a ≤415 V line, it handles about 23 kW of resistive load per pole. Don't use the AC-1 figure for motor starting; that would need an AC-3 rating (typically much lower for the same frame). The 4P configuration with mixed NO/NC poles gives flexibility for interlocking or dual-load circuits without adding auxiliary contact blocks. Mounts on DIN rail or a plate, so it fits standard panel layouts. IP2X protection means finger-safe from the front but not sealed — keep it inside an enclosure. It also meets GB/T equivalents for Chinese market installations. Operating altitude up to 3000 m means it can be used in high-altitude plants without derating — something not all contactors in this class offer.

The 93 mm depth is the key clearance dimension when fitting into a shallow enclosure; check that your panel depth accommodates it plus wiring space behind. DIN-rail mounting speeds replacement, but the plate-mount option works for back-panel layouts where rail space is tight.

Frequently asked questions

What are the key ratings of the LC1E32008M7IN?

It is a 4-pole contactor (2NO+2NC) rated AC-1 at 55 A up to 415 V with a 220 V coil. It is designed for resistive load switching and complies with EN/IEC 60947-1, -4-1, and -5-1 standards.

How should I source this obsolete contactor?

Since it's obsolete, source it through a distributor who can locate remaining inventory via surplus or broker channels. Submit an RFQ to confirm availability and pricing for your quantity.

What mounting options does the LC1E32008M7IN support?

It mounts on DIN rail or directly to a plate, giving flexibility for different panel layouts. The compact footprint (64×56×93 mm) fits standard enclosures.

MPN
LC1E32008M7IN