Schneider Electric LC1E3201F6 — Contactors

Schneider LC1E3201F6 Easy TeSys Contactor, 32A AC-3, 110V AC

MPNLC1E3201F6
Obsolete

Schneider Electric Easy TeSys Control, LC1E3201F6, 3P contactor, 32 A AC-3/AC-3e at ≤440 V, 110 V AC 60 Hz coil, 1 NC auxiliary contact.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E3201F6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E3201F6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E3201F6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E3201F6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E3201F6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E3201F6 — Mechanical
ParameterValue
Width56 mm
Height84 mm
Depth86 mm

Product details

It switches 32 A in AC-3 duty (≤440 V) and carries a 110 V AC 60 Hz coil with one normally-closed auxiliary contact built in. Fire resistance is verified to 850 °C per IEC 60695-2-1.

Mounts on a plate or DIN rail. Dimensions are 86 mm deep, 56 mm wide, 84 mm tall — fits a standard contactor footprint. IP2X finger protection on the enclosure. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation — important for interlocking circuits where simultaneous closure must be avoided.

Environmental and handling

Protective treatment TH (pollution degree 3) per IEC 60068-2-30 means it handles humid, polluted environments typical of industrial enclosures. Mechanical robustness: withstands 1.5 Gn vibration (5-300 Hz) when open, 3 Gn when closed; shock rated at 10 Gn for 11 ms closed, 6 Gn open.

Frequently asked questions

How do I source this part if it's obsolete?

Through the surplus and broker channel. Submit an RFQ and we will search our supply network for available stock.

What are the key ratings for this contactor?

32 A in AC-3/AC-3e duty at ≤440 V, 110 V AC 60 Hz coil, one NC auxiliary contact, 3 poles.

What standards does it comply with?

EN/IEC 60947-1, -4-1, -5-1 and GB/T 14048.1.4.5. Also referenced in EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for appliance applications.

MPN
LC1E3201F6