It switches 32 A in AC-3 duty (motor starting) at voltages up to 440 V, and carries a 110 V AC coil at 50/60 Hz. A single NC auxiliary contact is built in.
It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for fire resistance (850 °C glow-wire test per IEC 60695-2-1). The IP2X degree of protection means it is finger-safe but not sealed against dust or moisture — fit it inside a panel, not exposed.
Mounting and environment
Mechanical robustness is specified for vibration (1.5 Gn open, 3 Gn closed) and shock (10 Gn closed, 6 Gn open) — typical for industrial panel mounting near rotating machinery.