Skip to main content
Schneider Electric LC1E3201Q5 — Contactors

Schneider LC1E3201Q5 EasyPact TVS Contactor, 32A AC-3, 380V

MPNLC1E3201Q5
Obsolete

Schneider Electric EasyPact TVS, LC1E3201Q5, 3P contactor, 32 A AC-3 at ≤440 V, 380 V AC coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E3201Q5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E3201Q5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E3201Q5 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E3201Q5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E3201Q5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E3201Q5 — Mechanical
ParameterValue
Width56 mm
Height84 mm
Depth86 mm

Product details

The contactor is certified to EN/IEC 60947-4-1 for motor switching and EN/IEC 60947-5-1 for control circuit applications, with additional compliance to GB/T standards and IEC 60335-1 Clause 30.2 for fire resistance at 850 °C.

The AC-1 rating covers resistive loads at a higher current, but for motor duty, the AC-3 figure governs the selection. The 380 V AC coil matches standard European 380–400 V control circuits; verify your control voltage matches this nominal before specifying. It mounts on either a DIN rail or a plate, giving flexibility for panel integration. The protective treatment TH conforming to IEC 60068-2-30 test Db means it withstands damp heat conditions — relevant for tropical or non-conditioned environments.

Frequently asked questions

What standards does the LC1E3201Q5 comply with?

It is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards. It also meets IEC 60335-1 Clause 30.2 for fire resistance at 850 °C and has protective treatment TH per IEC 60068-2-30 for damp heat.

What is the coil voltage for the LC1E3201Q5?

The coil is rated for 380 V AC. Ensure your control circuit matches this nominal voltage before specifying.

How does the LC1E3201Q5 mount?

It supports both DIN rail and plate mounting, giving flexibility for panel integration.

MPN