The Schneider Electric LC1E3210F6 is a 3-pole contactor from the Easy TeSys Control range, rated for 32 A in AC-3 duty at ≤440 V — meaning it switches three-phase motor loads up to that current, with a 110 V AC 60 Hz coil and one normally-open auxiliary contact built in. It meets EN/IEC 60947-4-1 (contactor standard for motor starting) and EN/IEC 60947-5-1 (control circuit devices), plus GB/T equivalents, and carries IP2X finger protection on the contactor body.
Mounts on DIN rail or a plate. The NC-to-NO non-overlap time is guaranteed at 1.5 ms on both energisation and de-energisation — important for interlocking circuits where you need a break-before-make window.
No official successor order code is listed in the lifecycle record. For a BOM line that needs a drop-in replacement, a parametric cross-reference to a current Easy TeSys or TeSys Deca contactor with the same coil voltage and pole count is the practical path — confirm the auxiliary contact arrangement and mounting footprint against the panel layout.
Rated for operation at altitudes up to 3000 m without derating, and ambient temperature range of -5 °C to 55 °C operation, -20 °C to 70 °C at coil rated voltage, with storage down to -60 °C.