Skip to main content
Schneider Electric LC1E3210F6 — Contactors

Schneider Electric LC1E3210F6 Easy TeSys Contactor, 32A AC-3

MPNLC1E3210F6
Obsolete

Schneider Electric Easy TeSys Control, contactor, LC1E3210F6, 3P(3NO), AC-3/AC-3e ≤440V 32A, 110V AC coil 60Hz, 1NO auxiliary contact.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E3210F6 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E3210F6 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E3210F6 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E3210F6 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E3210F6 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E3210F6 — Mechanical
ParameterValue
Width56 mm
Height84 mm
Depth86 mm

Product details

The Schneider Electric LC1E3210F6 is a 3-pole contactor from the Easy TeSys Control range, rated for 32 A in AC-3 duty at ≤440 V — meaning it switches three-phase motor loads up to that current, with a 110 V AC 60 Hz coil and one normally-open auxiliary contact built in. It meets EN/IEC 60947-4-1 (contactor standard for motor starting) and EN/IEC 60947-5-1 (control circuit devices), plus GB/T equivalents, and carries IP2X finger protection on the contactor body.

Mounts on DIN rail or a plate. The NC-to-NO non-overlap time is guaranteed at 1.5 ms on both energisation and de-energisation — important for interlocking circuits where you need a break-before-make window.

No official successor order code is listed in the lifecycle record. For a BOM line that needs a drop-in replacement, a parametric cross-reference to a current Easy TeSys or TeSys Deca contactor with the same coil voltage and pole count is the practical path — confirm the auxiliary contact arrangement and mounting footprint against the panel layout.

Rated for operation at altitudes up to 3000 m without derating, and ambient temperature range of -5 °C to 55 °C operation, -20 °C to 70 °C at coil rated voltage, with storage down to -60 °C.

Frequently asked questions

What are the key ratings for the LC1E3210F6?

It is a 3-pole contactor rated 32 A in AC-3 (motor) duty at ≤440 V, with a 110 V AC 60 Hz coil and one normally-open auxiliary contact. It also carries AC-1 (resistive) and AC-3e utilisation categories.

What standards does the LC1E3210F6 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding GB/T standards, plus EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance applications.

MPN