Skip to main content
Schneider Electric LC1E38008V7IN — Contactors

Schneider Electric LC1E38008V7IN Easy TeSys Contactor, 4P, 6

MPNLC1E38008V7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E, 4P (2NO+2NC), AC-1, ≤415V, 60A (IN), 400V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1E38008V7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load

Ratings & Performance

LC1E38008V7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1

Contacts & Poles

LC1E38008V7IN — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

LC1E38008V7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E38008V7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5

Mechanical

LC1E38008V7IN — Mechanical
ParameterValue
Width56 mm
Height64 mm
Depth93 mm

Product details

The Schneider Electric LC1E38008V7IN is a 4-pole contactor from the Easy TeSys Control range, configured 2NO+2NC and rated for AC-1 resistive loads at 60 A up to 415 V. It is designed for switching resistive heating elements, lighting banks, or other non-inductive loads where inrush current is minimal — the AC-1 utilisation category (per EN/IEC 60947-4-1) defines this duty.

The AC-1 rating of 60 A at 415 V is the resistive-load current the main poles can carry continuously and interrupt without arc damage. Do not apply this contactor to motor or inductive loads at that current — AC-3 or AC-4 duty would require significant derating. The 4-pole arrangement (2NO+2NC) suits applications needing both normally-open and normally-closed power paths in one device, such as dual-speed heater stages or changeover circuits. Mechanical robustness is specified for vibration (3 Gn closed, 1.5 Gn open) and shock (10 Gn closed), which covers most industrial panel environments without additional damping. IP2X protection means the contactor body is finger-safe but not sealed against dust or moisture — it belongs inside an enclosure rated to the line environment.

Fire resistance tested to 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068, meaning it tolerates conductive pollution typical of industrial control rooms — not clean-room or outdoor exposure without an enclosure.

Frequently asked questions

What replaces the LC1E38008V7IN?

No official successor order code is listed in the lifecycle record. A replacement must be selected by matching pole count (4P, 2NO+2NC), coil voltage, and AC-1 current rating (60 A at 415 V) from the current Easy TeSys or TeSys Deca range.

What are the key ratings for this contactor?

AC-1 utilisation category, rated 60 A at up to 415 V for resistive loads. Four poles configured 2NO+2NC. Mounts on DIN rail or plate. Operating temperature range -5 to +55 °C.

What compliance documentation is available?

The contactor is designed to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and GB/T 14048 series. Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068.

MPN
LC1E38008V7IN