The coil is 220 V AC 50 Hz, wide-range control circuit type, with a drop-out threshold of 0.3 to 0.6 Uc and operational range of 0.7 to 1.25 Uc across -5 to 55 °C. Breaking capacity is 320 A at 440 V AC.
Mounts on DIN rail or plate. Dimensions are 85 mm wide, 127 mm high, 110 mm deep — a compact footprint for a 60 A 4-pole block. Power circuit terminals accept 2.5 to 25 mm² solid or flexible with cable end; control circuit terminals take 1 to 4 mm². Tightening torque is 5 N.m on the power side, 1.2 N.m on control. The IP2X finger protection means it is safe for open-panel mounting but not for washdown environments. Heat dissipation runs 6 to 10 W for the control circuit and 5.4 W per pole under AC-1 load. In a crowded DIN-rail enclosure, that thermal load needs to be factored into the cabinet cooling budget — especially if the contactor cycles near its maximum operating rate of 1200 cycles per hour at 60 °C.
Protective treatment is TH conforming to IEC 60068-2-30 (damp heat, cyclic). These certifications cover the contactor for industrial control panels in most global markets.