Skip to main content
Schneider Electric LC1E40008F7IN — Contactors

Schneider Electric LC1E40008F7IN Easy TeSys Contactor, 72A A

MPNLC1E40008F7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E40008F7IN, 4P (2NO+2NC) contactor, AC-1 ≤415V 72A, 110V coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E40008F7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E40008F7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E40008F7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E40008F7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E40008F7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E40008F7IN — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth110 mm

Product details

The Schneider Electric LC1E40008F7IN is a 4-pole (2NO+2NC) Easy TeSys Control contactor rated for 72 A in AC-1 utilisation category at up to 415 V, with a 110 V coil. AC-1 covers resistive loads — heaters, lighting banks, non-inductive circuits — so the 72 A figure is the continuous current it can make and break without arc damage. The 4-pole arrangement with two normally-open and two normally-closed contacts gives flexibility for switching both line and neutral or interlocking control circuits in the same package.

The 72 A AC-1 rating governs resistive loads only — do not apply this contactor to motor starting (AC-3) or inductive loads without derating. The 110 V coil means it pulls in reliably on a nominal 110 VAC control circuit; the permissible ambient range of -20 to 70 °C at coil rated voltage and -5 to 55 °C operation covers most indoor panel environments. IP2X finger protection means the contactor body prevents accidental contact with live parts but is not sealed against dust or moisture — mount inside a cabinet with at least IP54 enclosure for washdown areas.

Standards & mounting

Certified to EN/IEC 60947-1, 60947-4-1, and 60947-5-1 plus GB/T equivalents, so it meets the common panel-building standards for contactors and control circuit devices. Fire resistance tested to 850 °C per IEC 60695-2-1. TH protective treatment (pollution degree 3) per IEC 60068 means it handles typical industrial atmospheres with non-conductive dust and occasional condensation.

Frequently asked questions

What are the key ratings of the LC1E40008F7IN?

It is a 4-pole (2NO+2NC) contactor rated 72 A in AC-1 utilisation category at ≤415 V, with a 110 V coil. AC-1 covers resistive loads like heaters and lighting.

What standards does the LC1E40008F7IN comply with?

It complies with EN/IEC 60947-1, 60947-4-1, 60947-5-1, and the corresponding GB/T standards. Fire resistance is tested to 850 °C per IEC 60695-2-1.

How do I source the LC1E40008F7IN?

Since it is obsolete, sourcing is through surplus or broker channels. We can quote it to order against an RFQ — no shelf stock is maintained.

MPN
LC1E40008F7IN