It's rated for resistive loads under utilisation category AC-1, carrying 72 A at up to 415 V. That AC-1 rating means it's suited for switching resistive heaters, lighting banks, or other non-inductive loads where inrush is minimal — not motor starting, which would need an AC-3 rating.

Schneider Electric LC1E40008N7IN Easy TeSys Contactor, 4P, 7
MPNLC1E40008N7IN
Obsolete
Schneider Electric Easy TeSys Control, LC1E40008N7IN, 4P (2NO+2NC) contactor, AC-1 ≤415V 72A at 415V, plate/DIN-rail mount, IP2X.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Contactor |
| Series / range | Easy TeSys |
| Application | Resistive load |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | Power circuit: 10 MOhm for control circuit |
| Utilisation category | AC-1 |
| Parameter | Value |
|---|---|
| Pole configuration | 4P |
| Parameter | Value |
|---|---|
| IP degree of protection | IP2X conforming to IEC 60529 |
| Operating altitude | 3000 m |
| Mechanical robustness | Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms) |
| Protective treatment / pollution degree | TH (pollution degree 3) conforming to IEC 60068 |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 |
| Parameter | Value |
|---|---|
| Width | 85 mm |
| Height | 127 mm |
| Depth | 110 mm |
Product details
Frequently asked questions
What are the key ratings for this contactor?
4-pole (2NO+2NC), AC-1 utilisation category, rated 72 A at ≤415 V. Resistive load only. Mounts on plate or DIN rail, IP2X protection.
What standards does it comply with?
EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048.1, 14048.4, 14048.5. Fire resistance to 850 °C per IEC 60695-2-1.
MPN
LC1E40008N7IN