Skip to main content
Schneider Electric LC1E40B01M7 — Contactors

Schneider Electric LC1E40B01M7 Easy TeSys Contactor, 40A AC-

MPNLC1E40B01M7
Active

Schneider Electric Easy TeSys contactor, LC1E40B01M7, 3P (3 NO), AC-3 40A at 440V, 220V AC coil, DIN rail mount, active production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E40B01M7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E40B01M7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E40B01M7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E40B01M7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E40B01M7 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E40B01M7 — Mechanical
ParameterValue
Width56 mm
Height84 mm
Depth86 mm

Product details

The Schneider Electric LC1E40B01M7 is an Easy TeSys contactor — a 3-pole (3 NO) motor-switching device rated 40 A in AC-3 duty at up to 440 V, with a 220 V AC coil.

The AC-3 rating of 40 A at 440 V is the number that governs motor switching — it means the contactor can make and break a 3-phase induction motor load up to that current, covering most 18.5 kW motors at 400 V. AC-1 (resistive) and AC-3e (enhanced motor) categories are also listed, giving flexibility for heater banks or high-efficiency motor starts. The 220 V AC coil is common in European and Asian control circuits; verify your control voltage matches before panel integration, as coil burn-out is a common commissioning error. The IP2X degree of protection means it's finger-safe but not sealed; install inside an enclosure for washdown or dusty environments. Operating altitude goes to 3000 m without derating, useful for high-altitude installations. Mechanical robustness is specified: vibrations at 1.5 Gn (open) and 3 Gn (closed) over 5–300 Hz, and shocks at 6 Gn (open) and 10 Gn (closed) for 11 ms. These numbers matter for applications on conveyors, shuttle systems, or mobile equipment where the contactor sees continuous vibration.

Also complies with EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance safety. These standards make it acceptable for industrial panels and HVAC equipment in most markets.

Frequently asked questions

What are the key ratings I need to check for fit?

The critical rating is 40 A in AC-3 duty at up to 440 V, which governs motor switching. The coil is 220 V AC. Mounting is DIN rail or plate, dimensions are 84 x 56 x 86 mm (H x W x D). Operating temperature range is -5 to 55 °C, with storage from -60 to 80 °C.

What compliance documentation does this contactor carry?

It is certified to EN/IEC 60947-1, -4-1, -5-1, and the Chinese GB/T 14048 series. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance safety. Fire resistance is tested at 850 °C per IEC 60695-2-1.

MPN