The coil is wound for 415 V AC, common on European 400 V three-phase networks.
If you need a form-fit-function replacement within the Easy TeSys family, the closest active sibling shares the same frame size and mounting footprint but differs in coil voltage or certification revision — check the spec line yourself against your panel's coil supply and ambient temperature range.
The 56 mm width and 84 mm height fit a standard contactor slot in a motor control centre; depth is 86 mm, which clears most 100 mm deep enclosures. Rated for operation at up to 3000 m altitude without derating, and ambient air temperature from -20 to 70 °C at the coil rated voltage, with storage down to -60 °C. The IP2X degree of protection means it is finger-safe but not sealed; install inside a panel with a higher enclosure rating for washdown or outdoor duty.