It carries AC-3, AC-3e, and AC-1 utilisation categories, meaning it handles both motor starting and resistive heating loads. The AC-3/AC-3e rating at ≤440 V is 50 A — that is the current it can make and break across a motor load cycle without accelerated contact wear. The coil is 220 V AC, 50 Hz, so it pulls in cleanly on a standard European control voltage. Non-overlap time of 1.5 ms on both energisation and de-energisation guarantees NC and NO contacts never close simultaneously — a safety detail when interlocking two contactors.
Mounts on either a DIN rail or a plate — the evidence lists both options, so it fits a standard panel backplate or a DIN-rail assembly. Dimensions are 75 mm wide, 127 mm high, 114 mm deep, which is the typical Easy TeSys footprint for this current class. IP2X protection means it is finger-safe from the front but not sealed against dust ingress — it belongs inside an enclosure, not in a washdown zone.
Rated for operation from -5 °C to 55 °C ambient, with storage from -60 °C to 80 °C. No derating needed up to 3000 m altitude. The TH protective treatment (pollution degree 3) means it withstands humid, mildly corrosive environments per IEC 60068-2-30 — typical for non-condensing industrial panels. Compliant with EN/IEC 60947-4-1 (contactor standard for motor starters), EN/IEC 60947-5-1 (control circuit devices), and GB/T equivalents for the Chinese market. Fire resistance tested to 850 °C per IEC 60695-2-1.