Skip to main content
Schneider Electric LC1E50Q7 — Contactors

Schneider EasyPact TVS LC1E50Q7 Contactor, 3P, AC-3 50A, 380

MPNLC1E50Q7
Active

Schneider Electric EasyPact TVS contactor, 3P (3 NO), AC-3 ≤440 V 50 A, 380 V AC coil, DIN rail/plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E50Q7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E50Q7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E50Q7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E50Q7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E50Q7 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E50Q7 — Mechanical
ParameterValue
Width75 mm
Height127 mm
Depth114 mm

Product details

The 380 V AC coil matches standard European industrial control voltages.

The headline AC-3 rating of 50 A at ≤440 V governs motor switching: AC-3 is the category for starting and stopping squirrel-cage induction motors under load, so this contactor handles inrush up to about 6× rated current during start. The AC-3e rating extends that to energy-efficient motors with higher inrush. For purely resistive loads (heater banks, lighting), the AC-1 rating applies — no inrush, so the thermal capacity is the limit. The 1.5 ms non-overlap time between NC and NO contacts on both energisation and de-energisation ensures the auxiliary contacts never bridge during transition, critical for interlocking in reversing or star-delta circuits.

IP2X means finger-safe from the front but not sealed; install inside an enclosure rated for the environment. The TH protective treatment (pollution degree 3) per IEC 60068-2-30 means it withstands the condensation and humidity cycles typical of non-climate-controlled industrial panels.

Frequently asked questions

What are the key ratings for the LC1E50Q7?

AC-3 rated 50 A at ≤440 V for motor loads, with a 380 V AC coil. Also rated AC-3e and AC-1. Three-pole, three normally-open main contacts.

What standards does the LC1E50Q7 comply with?

Compliant with EN/IEC 60947-1, -4-1, -5-1 and the Chinese GB/T 14048.1.4.5. Fire resistance tested to 850 °C per IEC 60695-2-1.

How is the LC1E50Q7 mounted?

DIN rail or plate mount. Dimensions are 75 mm wide, 127 mm high, 114 mm deep.

MPN
LC1E50Q7