Skip to main content
Schneider Electric LC1E600BSCT1S260N — Contactors

Schneider LC1E600BSCT1S260N DC Contactor, 600 A, 1500 V

MPNLC1E600BSCT1S260N
Active

Schneider Electric Easy TeSys DC contactor, LC1E600BSCT1S260N, 600 A continuous rated, 1500 V DC switching, 24 V DC coil, 1-pole normally open.

$1,000.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1E600BSCT1S260N — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E600BSCT1S260N — Contacts & Poles
ParameterValue
Pole configuration1P
LC1E600BSCT1S260N — Environmental
ParameterValue
IP degree of protectionIP60
Operating altitude13123.36 ft (4000 m) without derating
Mechanical robustnessVibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)
LC1E600BSCT1S260N — Approvals
ParameterValue
StandardsIEC 60947-4-1 GB/T 14048.4
LC1E600BSCT1S260N — Mechanical
ParameterValue
Width2.8 in (70 mm)
Height4.2 in (107.9 mm)
Depth4.09 in (104 mm)

Product details

The LC1E600BSCT1S260N: Mounts vertically on a panel or DIN rail (dedicated Easy TeSys support). Power terminals accept M8 nut with flat and spring washers; tighten to 8–10 N·m. Control wiring is a 30 cm pre-wired 2-wire supply (11.8 in). At IP60, it's sealed against dust—suitable for control cabinets but not for washdown areas. Operating temperature range -40 to 85 °C, so it lives comfortably in both hot attics and cold storage yards.

Overload tolerance and durability

Rated short-time current: 600 A continuous, 750 A for 15 minutes, 900 A for 120 seconds, and a pulse of 8000 A for 5 ms without fire or explosion—critical for surviving brief fault conditions. Mechanical life is 300,000 cycles, and it withstands 5 g vibration (10–500 Hz) and 20 g shock for 11 ms. For resistive-load switching at maximum voltage, expect 1000 cycles at 750 V / 600 A breaking and 800 cycles at 1000 V / 600 A.

Frequently asked questions

What is the maximum DC switching voltage?

1500 V DC, rated for resistive load breaking.

What compliance standards does it meet?

It complies with IEC 60947-4-1 and GB/T 14048.4, and carries an impulse withstand voltage of 8 kV (coil not connected to power circuit).

What is the depth of this contactor?

Listed depth is 4.09 in (104 mm).

MPN
LC1E600BSCT1S260N