Skip to main content
Schneider Electric LC1E65004M5WB — Contactors

Schneider Electric LC1E65004M5WB Easy TeSys Contactor, 80 A

MPNLC1E65004M5WB
Obsolete

Schneider Electric Easy TeSys, LC1E65004M5WB, 4-pole contactor, 80 A AC-1, 220 V AC 50 Hz coil, screw terminals, DIN rail / plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E65004M5WB — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E65004M5WB — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E65004M5WB — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E65004M5WB — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E65004M5WB — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E65004M5WB — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth125 mm

Product details

Coil is 220 V AC at 50 Hz, wide-range AC control. It pulls 160 VA inrush at 20 °C and settles to a heat dissipation of 6–10 W in the control circuit. Drop-out threshold is 0.3–0.6 Uc; pick-up is 0.7–1.25 Uc. That wide hold-in margin means the contactor stays closed through brief sags on a 220 V line — useful if your control transformer is feeding other loads.

Dimensions are 85 mm wide, 127 mm high, 125 mm deep — a standard footprint for a four-pole frame in this range. Tightening torque is 5 N·m on the power side, 1.2 N·m on control.

Durability and mechanical robustness

Mechanical durability is rated at 5 million cycles; electrical durability is 350,000 cycles at AC-1 load. Maximum operating rate is 1200 cycles per hour at 60 °C. Vibration resistance: 1.5 Gn contactor open, 3 Gn closed across 5–300 Hz. Shock resistance: 6 Gn open, 7 Gn closed for 11 ms. These specs mean the contactor can live on a high-cycle conveyor or compressor start-stop duty without premature mechanical fatigue.

Complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, plus the GB/T equivalents for China. Protective treatment TH conforming to IEC 60068-2-30 (damp heat cyclic). IP2X finger protection on the front face.

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current 80 A at ≤440 V AC in AC-1 (resistive load). Rated insulation voltage 690 V. Coil voltage 220 V AC 50 Hz. Four normally-open power poles. Screw terminals for both power and control circuits.

Does this contactor include auxiliary contacts?

No. The LC1E65004M5WB ships without auxiliary contacts. Auxiliary contact blocks can be added separately if needed.

What standards does the LC1E65004M5WB comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T 14048.1, 14048.4, and 14048.5 equivalents. It also meets IP2X front-face protection and 850 °C glow-wire fire resistance.

MPN
LC1E65004M5WB