Skip to main content
Schneider Electric LC1E65008B7IN — Contactors

Schneider LC1E65008B7IN Easy TeSys Contactor, 85A AC-1, 24V,

MPNLC1E65008B7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E65008B7IN, 4P contactor, AC-1 ≤415V 85A, 24V coil, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1E65008B7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E65008B7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E65008B7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E65008B7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E65008B7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E65008B7IN — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth125 mm

Product details

The LC1E65008B7IN is a 4-pole (2NO+2NC) contactor from the Schneider Easy TeSys Control range, rated for 85 A in AC-1 utilisation category at ≤415 V with a 24 V coil. AC-1 means it is designed for resistive loads — heaters, lighting banks, or other loads where the current waveform stays close to sinusoidal and inrush is minimal. That 85 A rating is the full-load current it can make and break under those conditions, not a motor-starting figure.

Mounts on a plate or DIN rail, which means it slots into a standard control-panel layout alongside other Easy TeSys or third-party gear. The 85 mm width and 127 mm height leave room for adjacent devices in a crowded enclosure.

Fire resistance rated to 850 °C per IEC 60695-2-1. The protective treatment is TH (pollution degree 3) per IEC 60068, meaning it handles typical factory-floor contamination without creeping discharge. Operates from -5 °C to 55 °C ambient and stores from -60 °C to 80 °C, with a 3000 m altitude limit — fine for most indoor industrial sites.

Frequently asked questions

What replaces the LC1E65008B7IN?

There is no official successor order code in the lifecycle record. A replacement would need to be selected by matching the 85 A AC-1 rating, 4-pole configuration, 24 V coil, and DIN-rail footprint against current Easy TeSys or TeSys D catalog numbers.

What are the key ratings of this contactor?

85 A in AC-1 (resistive load) at ≤415 V, 4 poles (2NO+2NC), 24 V coil. Mounts on DIN rail or plate. Compliant with EN/IEC 60947 series.

How do I source this obsolete part?

Since it is obsolete, the only channel is surplus or independent distributor stock. Submit an RFQ for a quote on available new-old-stock units.

MPN
LC1E65008B7IN