Specifications

LC1E65008M5WB — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E65008M5WB — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E65008M5WB — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E65008M5WB — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30 test Db
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E65008M5WB — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E65008M5WB — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth125 mm

Product details

The Schneider Electric LC1E65008M5WB is a 4-pole contactor from the Easy TeSys Control range, rated for 80 A in AC-1 utilisation category (resistive loads) at up to 440 V. The coil is 220 V AC 50 Hz wide-range, with a drop-out threshold of 0.3 to 0.6 Uc and operational range of 0.7 to 1.25 Uc across -5 to 55 °C.

For motor starting (AC-3 duty), you would need to derate; the part is not listed with an AC-3 rating in this evidence. The 4-pole configuration (2 NO + 2 NC) gives flexibility for switching multiple circuits or implementing interlocking without adding auxiliary contact blocks — the auxiliary contact composition is listed as 'without', so the main poles are the only switching elements. Mechanical durability is 5 million cycles, and electrical durability is 350,000 cycles at AC-1 — a solid lifespan for a resistive-load contactor in continuous-duty applications like conveyor heaters or industrial ovens. The maximum operating rate of 1200 cycles per hour at 60 °C means it can handle frequent switching if needed.

This class of contactor is used in industrial control panels for switching resistive loads — heating elements, lighting banks, or transformer primaries — where the current is sinusoidal and inrush is minimal. The IP2X finger protection and pollution degree 3 rating suit it for general industrial environments, not clean rooms or wet areas.

Frequently asked questions

What are the key ratings for this contactor?

The key ratings are 80 A rated operational current in AC-1 (resistive loads) at ≤440 V, a 220 V AC 50 Hz coil, 4-pole configuration (2 NO + 2 NC), mechanical durability of 5 million cycles, and electrical durability of 350,000 cycles at AC-1.

What compliance standards does it meet?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5. Fire resistance is 850 °C per IEC 60695-2-1, and protective treatment is TH conforming to IEC 60068-2-30 test Db.

MPN