Specifications

LC1E80004M5WBIN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E80004M5WBIN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E80004M5WBIN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E80004M5WBIN — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E80004M5WBIN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E80004M5WBIN — Mechanical
ParameterValue
Width95 mm
Height127 mm
Depth120 mm

Product details

It carries a rated operational current of 110 A at up to 415 V AC, with 4 normally open main poles and a 220 V AC 50 Hz control coil. No auxiliary contacts are fitted on this variant.

Rated insulation voltage is 690 V, and the contactor can make 800 A and break 640 A at 440 V — figures that confirm it handles inrush and fault clearing within its AC-1 envelope. The control coil draws 200 VA inrush at 50 Hz and dissipates 6 to 10 W in steady state, which matters for transformer sizing in the panel.

Power terminals accept 4 to 50 mm² solid or flexible with cable end; control terminals take 1 to 4 mm². Tighten power connections to 12 N·m and control wires to 1.2 N·m — that torque on the screw clamp terminals keeps the joint stable under load cycling.

Compliant with EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents. Protective treatment TH per IEC 60068 for tropical environments.

Durability and operating conditions

Rated for 350,000 electrical cycles in AC-1 and 3,000,000 mechanical cycles. Maximum operating rate is 1,200 cycles per hour at 60 °C. Withstands vibration up to 3 Gn when closed and shocks up to 7 Gn — figures that matter if the panel is mounted on a machine frame. Operating altitude goes to 3,000 m without derating.

Frequently asked questions

What compliance documentation does Schneider provide for this part?

The contactor is certified to EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents. It carries protective treatment TH per IEC 60068 for tropical environments and fire resistance to 850 °C per IEC 60695-2-1. Schneider typically provides a declaration of conformity covering these standards with the shipment.