Schneider LC1E80004M7IN Easy TeSys Contactor, 4P, AC-1 110A,

MPNLC1E80004M7IN
Obsolete

Schneider Electric Easy TeSys Control, LC1E80004M7IN, 4-pole contactor, AC-1 110 A at ≤415 V, 220 V coil, plate/DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E80004M7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E80004M7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E80004M7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E80004M7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E80004M7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E80004M7IN — Mechanical
ParameterValue
Width95 mm
Height127 mm
Depth120 mm

Product details

The Schneider Electric LC1E80004M7IN is a 4-pole contactor from the Easy TeSys Control range, rated for AC-1 resistive load duty at 110 A up to 415 V, with a 220 V coil. It switches resistive loads — heaters, lighting banks, or transformer primaries — where inrush is low and the current curve stays clean. The 4-pole arrangement gives you two normally-open and two normally-closed main contacts, which is useful for splitting a load across phases or for two-wire control circuits that need a break before make.

The AC-1 utilisation category is the key rating: it certifies the contactor for resistive loads where the current is nearly in phase with voltage, so there is minimal arcing at break. That 110 A at ≤415 V is the full-load continuous current the main poles can carry and interrupt under those conditions. If your load is motor (AC-3) or inductive (AC-4), this contactor is not rated for that duty — the inrush and arc energy would exceed its design limits. The 220 V coil is a standard control voltage in many industrial panels, but it is not a dual-voltage coil — it pulls in and holds at 220 V nominal. The 850 °C glow-wire test (IEC 60695-2-1) confirms the housing material resists ignition under fault conditions.

Frequently asked questions

What are the key ratings of the LC1E80004M7IN?

It is a 4-pole contactor (2NO+2NC) rated AC-1 at 110 A up to 415 V, with a 220 V coil. It mounts on a plate or DIN rail and has IP2X finger protection.

What standards does the LC1E80004M7IN comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents. The housing passes the 850 °C glow-wire test per IEC 60695-2-1.

How do I source the LC1E80004M7IN if it is obsolete?

Since it is obsolete, the part is sourced through surplus or independent channels. Submit an RFQ with your quantity and target price; we will check our network of new-old-stock and pulled-from-stock inventory.

MPN