Skip to main content
Schneider Electric LC1E80004V7IN — Contactors

Schneider Electric LC1E80004V7IN Easy TeSys Contactor, 4P, A

MPNLC1E80004V7IN
Obsolete

Schneider Electric Easy TeSys Control LC1E80004V7IN, 4P(4NO) contactor, AC-1 <=415V 110A, 400V coil, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E80004V7IN — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E80004V7IN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-1
LC1E80004V7IN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E80004V7IN — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E80004V7IN — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E80004V7IN — Mechanical
ParameterValue
Width95 mm
Height127 mm
Depth120 mm

Product details

The LC1E80004V7IN is a 4-pole (4NO) contactor from the Easy TeSys Control range, rated for 110 A in AC-1 utilisation category at up to 415 V. AC-1 covers resistive loads — heaters, lighting banks, non-inductive circuits — so this contactor is sized for switching those loads, not motor starting. The 400 V coil suits standard three-phase control voltages across 50/60 Hz panels. Mounting is flexible: plate or DIN rail. The 95 mm width and 127 mm height fit a standard contactor footprint on the rail, leaving room for auxiliary blocks alongside. IP2X finger protection is the minimum for enclosed gear — fine inside a panel, not for open washdown areas.

Rated operational voltage for the power circuit is given as 10 MOhm for the control circuit — that is the insulation resistance test value, not a working voltage. The contactor is built to EN/IEC 60947-4-1 and GB/T 14048.4, which cover contactors and motor-starters.

Frequently asked questions

What are the key ratings of the LC1E80004V7IN?

It is a 4-pole (4NO) contactor rated for 110 A in AC-1 utilisation category at up to 415 V, with a 400 V coil. It mounts on plate or DIN rail and complies with EN/IEC 60947 and GB/T 14048 standards.

What compliance documentation does Schneider provide for this contactor?

The part is certified to EN/IEC 60947-1, -4-1, -5-1 and the equivalent GB/T 14048.1.4.5 standards. It also meets IEC 60695-2-1 for fire resistance at 850 °C and IEC 60068 for TH protective treatment (pollution degree 3).

MPN
LC1E80004V7IN