Skip to main content
Schneider Electric LC1E80008M5WB — Contactors

Schneider Electric LC1E80008M5WB Easy TeSys Contactor, 100 A

MPNLC1E80008M5WB
Obsolete

Schneider Electric Easy TeSys Control LC1E80008M5WB, 4-pole contactor, 100 A AC-1 at ≤440 V, 220 V AC 50 Hz coil, DIN rail or plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E80008M5WB — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationResistive load
LC1E80008M5WB — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: <= 690 V AC 50/60 Hz
Utilisation categoryAC-1
LC1E80008M5WB — Contacts & Poles
ParameterValue
Pole configuration4P
LC1E80008M5WB — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E80008M5WB — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5
LC1E80008M5WB — Mechanical
ParameterValue
Width95 mm
Height127 mm
Depth120 mm

Product details

The Schneider Electric LC1E80008M5WB is a 4-pole contactor from the Easy TeSys Control range, rated for 100 A in AC-1 duty at ≤440 V — that's the resistive load curve, so it's sized for heaters, lighting banks, or other non-inductive circuits where inrush stays low. The 220 V AC 50 Hz coil pulls 200 VA inrush at 50 Hz, then settles to 6–10 W heat dissipation on the control side. Pole composition is 2 NO + 2 NC, with no built-in auxiliary contacts — you add those separately if the circuit needs feedback or interlocking. Rated insulation voltage hits 690 V, and the breaking capacity at 440 V is 640 A, so it clears faults cleanly within its AC-1 envelope.

Power terminals accept up to 50 mm² cable (solid or flexible with ferrule), torqued to 12 N·m. Control-circuit screw clamps take 1–4 mm² at 1.2 N·m. IP20 finger-safe protection is fine for enclosed panels; not rated for washdown environments.

AC-1 at 100 A is the headline number — it's the thermal current the main poles carry continuously in resistive service. Don't substitute a motor-rated (AC-3) contactor here unless you verify the coil and pole count match; this part is specced for resistive loads, not inductive motor starts. Mechanical durability is 3 million cycles, electrical durability 350,000 cycles at AC-1 — so it's built for frequent switching in oven or furnace control, not a once-a-day pump start. Operating altitude goes to 3000 m without derating, so it works in high-elevation plants without a current haircut.

Frequently asked questions

What are the key ratings for this contactor?

Rated operational current is 100 A at ≤440 V AC in AC-1 (resistive) duty. Rated insulation voltage is 690 V. Breaking capacity at 440 V is 640 A. The coil is 220 V AC 50 Hz with a 200 VA inrush.

What compliance standards does this part meet?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, GB/T 14048.1, GB/T 14048.4, and GB/T 14048.5. Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068-2-30.

What is the mounting and wiring specification?

Mounts on DIN rail or plate. Power terminals accept 4–50 mm² cable, torqued to 12 N·m. Control terminals accept 1–4 mm², torqued to 1.2 N·m. IP20 protection rating.

MPN
LC1E80008M5WB