Specifications

Identification

LC1E80M5 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load

Ratings & Performance

LC1E80M5 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1

Contacts & Poles

LC1E80M5 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1E80M5 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1

Approvals

LC1E80M5 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ

Mechanical

LC1E80M5 — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth121 mm

Product details

The LC1E80M5 is a 3-pole contactor from Schneider Electric's Easy TeSys Control range, rated 80 A in AC-3 and AC-3e utilisation categories at ≤440 V. The 220 V AC 50 Hz coil pulls in cleanly on a standard control transformer, and the 1.5 ms guaranteed non-overlap time between NC and NO contacts means you won't get a cross-conduction glitch during coil energisation or de-energisation.

Mounts on either a DIN rail or a plate, so it slots into a standard control panel without a special adapter. Dimensions are 85 mm wide by 127 mm tall by 121 mm deep — that's a compact footprint for an 80 A motor-rated contactor. The IP2X finger-safe degree of protection means it's fine inside an enclosed panel; you don't need to add terminal shrouds for basic touch protection.

Certified to EN/IEC 60947-4-1 (the main contactor standard for motor starting) and EN/IEC 60947-5-1 for control-circuit switching, plus the GB/T equivalents. That means it's accepted across European and Chinese markets without a separate approval run. Fire resistance tested to 850 °C glow-wire per IEC 60695-2-1, and the TH protective treatment (pollution degree 3) handles the condensation and humidity you'd see in an unheated panel room.

Frequently asked questions

What utilisation categories does this contactor cover?

It is rated for AC-3 and AC-3e (motor starting) and AC-1 (resistive load). The AC-3 rating at 80 A, ≤440 V is the one that governs motor duty.

What coil voltage does the LC1E80M5 use?

The coil is 220 V AC, 50 Hz. There is no DC or dual-frequency variant in this order code.

What compliance documentation is available for this part?

It is certified to EN/IEC 60947-1, -4-1, and -5-1, plus the Chinese GB/T equivalents. Fire resistance is 850 °C per IEC 60695-2-1. The TH protective treatment meets IEC 60068-2-30 for damp heat.