Skip to main content
Schneider Electric LC1E80M7 — Contactors

Schneider Electric LC1E80M7 EasyPact TVS Contactor, 80A AC-3

MPNLC1E80M7
Active

Schneider Electric EasyPact TVS, LC1E80M7, 3-pole contactor, AC-3 80A ≤440V, 220V AC coil, DIN rail/plate mount.

$135.15Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E80M7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeEasy TeSys
ApplicationMotor control Resistive load
LC1E80M7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 10 MOhm for control circuit
Utilisation categoryAC-3 AC-3e AC-1
LC1E80M7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1E80M7 — Environmental
ParameterValue
IP degree of protectionIP2X conforming to IEC 60529
Operating altitude3000 m without derating
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Protective treatment / pollution degreeTH (pollution degree 3) conforming to IEC 60068-2-30
Fire resistance850 °C conforming to IEC 60695-2-1
LC1E80M7 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ
LC1E80M7 — Mechanical
ParameterValue
Width85 mm
Height127 mm
Depth121 mm

Product details

Its AC-3 rating is 80 A at ≤440 V — the current it can switch a three-phase induction motor under full load.

Where it fits in a panel

The 85 mm width and 127 mm height keep it compact for a 3-pole contactor at this rating.

Environmental tolerance and compliance

The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it withstands humid, mildly corrosive atmospheres — typical in HVAC or pump rooms, but not for direct washdown zones. Standards compliance covers EN/IEC 60947-4-1 (the main contactor standard), plus GB/T equivalents for Chinese markets.

Frequently asked questions

What mounting options does this contactor support?

It mounts on a DIN rail or directly to a backplate with screws. The 85 mm width fits standard DIN-rail spacing, and the plate-mount option allows fixed installation in panels without a rail.

What compliance standards does the LC1E80M7 meet?

It complies with EN/IEC 60947-1, EN/IEC 60947-4-1 (the main contactor product standard), EN/IEC 60947-5-1, plus the Chinese GB/T equivalents 14048.1, 14048.4, and 14048.5. It also meets the glow-wire test at 850 °C per IEC 60695-2-1 for fire resistance.

MPN
LC1E80M7