The coil is 48 V AC, so it pulls in and holds on a 48 VAC control supply. The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation — this prevents shoot-through in reversing or star-delta circuits where the two contactors must never close simultaneously.
Where it fits and how it mounts
Dimensions are 85 mm wide, 127 mm high, 121 mm deep — fits a standard contactor footprint for this current class. IP2X protection means the contactor body is finger-safe but not sealed against moisture; it belongs in a clean, dry enclosure, not a washdown zone.
Environmental and compliance profile
The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it withstands humid, corrosive atmospheres — typical for industrial panels in non-conditioned plant floors. Operates without derating up to 3000 m altitude, and meets mechanical robustness of 1.5 Gn vibration (contacts open) and 3 Gn (closed), plus shock ratings of 6 Gn open and 7 Gn closed. Fire resistance tested to 850 °C per IEC 60695-2-1. Compliant with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048 series, and relevant clauses of EN/IEC 60335 for household appliance safety — so it is accepted across European, Chinese, and many other regulatory jurisdictions.