The 4 NO pole configuration and AC 60 Hz control coil define its wiring pattern: all four poles close together when the coil pulls in.
The rated operational current is 200 A at ≤440 V AC-1.
The contactor is certified to EN 60947-4-1, IEC 60947-4-1, EN 60947-1, IEC 60947-1, and JIS C8201-4-1. The IP2X front-face protection with shrouds keeps fingers out — standard for open-panel mounting. Protective treatment TH indicates tropicalisation for humid environments.
Mounting is plate-mount, not DIN rail — this is a bolted-down contactor for a panel backplate. Dimensions: 6.4 in (162 mm) high, 7.9 in (200.5 mm) wide, 6.7 in (171 mm) deep. Power connections are bolted bars or ring terminals up to 95 mm²; control circuit terminals accept 1–4 mm² solid or flexible wire with screw clamps. Tightening torque: 10 N·m on the power circuit, 1.2 N·m on the control circuit.