Skip to main content
Schneider Electric LC1F115B622L — Contactors

Schneider Electric LC1F115B622L TeSys F Contactor, 200 A AC-

MPNLC1F115B622L
Obsolete

Schneider Electric TeSys F contactor, LC1F115B622L, 3-pole, 200 A AC-3 rated operational current, 24 V AC 60 Hz coil, 2 NO + 2 NC auxiliary contacts, end-of-life status.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F115B622L — Identification
ParameterValue
Product / component typeContactor
ApplicationMotor control Resistive load
LC1F115B622L — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1 AC-3
LC1F115B622L — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F115B622L — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms
Protective treatment / pollution degreeTH
LC1F115B622L — Approvals
ParameterValue
StandardsJIS C8201-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1 IEC 60947-4-1
LC1F115B622L — Mechanical
ParameterValue
Width6.4 in (163.3 mm)
Height10.4 in (265 mm)
Depth6.7 in (171 mm)

Product details

TeSys F Contactor — LC1F115B622L

For a quick fit check: this contactor delivers 55 kW at 380–400 V AC, 59 kW at 415/440 V, and 75 kW at 500 V; on UL/CSA duty it's rated 75 hp at 460 V AC and 100 hp at 575 V AC. The coil is 24 V AC 60 Hz (Uc), with an operational range of 0.85–1.1 Uc and a drop-out band of 0.35–0.55 Uc at 55 °C. Auxiliary contacts are built in as 2 NO + 2 NC.

The LC1F115B622L carries approvals to IEC 60947-4-1, EN 60947-4-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Overvoltage category III. The front face with shrouds achieves IP2X per IEC 60529 and VDE 0106. Protective treatment is TH (tropicalized).

Integration Notes

Mounting is plate-based (not DIN rail), so plan for a backplate or sub-panel in the enclosure. Power circuit connections accept two bars (20 x 3 mm), ring terminals up to 95 mm², or a connector for 95 mm². Control circuit terminals are screw-clamp, accepting 1–4 mm² flexible or solid (without cable end) or 1–2.5 mm² flexible with cable end. Tightening torque: power circuit 10 N·m, control circuit 1.2 N·m. Dimensions: 6.7 in (171 mm) deep, 6.4 in (163.3 mm) wide, 10.4 in (265 mm) high. Heat dissipation is 12–16 W total; per pole it's 15 W in AC-1 and 5 W in AC-3. Associated fuse rating: 125 A aM or 200 A gG at ≤ 440 V.

Frequently asked questions

Where can I buy LC1F115B622L?

We source this EOL contactor to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position.

What are the key ratings for LC1F115B622L?

Rated operational current (Ie) is 200 A at ≤ 440 V AC in AC-3 duty. Motor power is 55 kW at 400 V, 75 kW at 500 V, and 80 kW at 690 V. Coil voltage is 24 V AC 60 Hz. Auxiliary contacts: 2 NO + 2 NC.

What is the closest alternative to LC1F115B622L?

A form-fit-function alternative would be another TeSys F contactor in the same frame size and AC-3 current class (200 A), but with a different coil voltage or auxiliary contact arrangement. Check the spec line yourself — the coil voltage (24 V AC 60 Hz) and the 2 NO + 2 NC aux configuration are the binding constraints for a drop-in swap.

MPN
LC1F115B622L