Skip to main content
Schneider Electric LC1F1400ED — Contactors

Schneider Electric LC1F1400ED TeSys F Contactor, 1400 A AC-1

MPNLC1F1400ED
Obsolete

Schneider Electric TeSys F, LC1F1400ED, 3-pole contactor, 1400 A AC-1 rated operational current, 48 V DC control coil, plate mount, depth 238.6 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F1400ED — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F1400ED — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F1400ED — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F1400ED — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F1400ED — Approvals
ParameterValue
StandardsIEC 60947-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F1400ED — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

What the 1400 A AC-1 rating means for your load

The LC1F1400ED is a TeSys F three-pole contactor rated for 1400 A in AC-1 utilisation category (resistive load) at ≤40 °C ambient. That AC-1 rating governs continuous current through the main poles for heating elements, lighting banks, or transformer primary switching — not motor starting. The conventional free-air thermal current (Ith) matches at 1400 A, so there is no hidden derating between the two numbers; what you read is what the bar carries. The control coil pulls 48 V DC, with a hold-in consumption of 10 W at 20 °C and an inrush of 2100 W. The pick-up and drop-out window is wide: it operates between 0.85 and 1.1 Uc and drops out between 0.3 and 0.5 Uc, which gives you margin on a sagging DC bus.

Standards and compliance — what the approvals certify

This contactor carries IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 compliance. That means it is listed for both IEC and North American markets without a separate UL/CSA variant. The short-time withstand ratings (Icw) are 8000 A for 10 s, 6000 A for 30 s, and 4500 A for 1 min at 40 °C — these numbers govern coordination with upstream fuses or breakers during a fault. The associated fuse recommendation is 1600 A gG at ≤440 V.

Mounting and integration — plate mount, not DIN rail

Mounting support is plate (bolted), not DIN rail. The footprint is 438 mm wide by 332 mm high by 238.6 mm deep — a large frame that needs a backplate or sub-panel, not a standard enclosure rail. Power connections are bar-type with bolted terminals torqued to 58 N·m; control wiring uses screw-clamp terminals torqued to 1.2 N·m. Heat dissipation is 10 W total at rated current, with 150 W per pole in AC-1 duty. That is significant for panel thermal calculations — the 438 mm width and plate mount are designed to shed that heat through the backplate, not through convection slots.

Frequently asked questions

What compliance documentation does the LC1F1400ED carry?

The LC1F1400ED complies with IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. It also meets VDE 0110 group C for insulation coordination at 1500 V.

What is the LC1F1400ED's depth dimension?

The LC1F1400ED has a depth of 238.6 mm, a width of 438 mm, and a height of 332 mm. It is a plate-mount contactor, not DIN-rail compatible.

What is the closest alternative to the LC1F1400ED in the TeSys family?

No direct successor order code is listed in the manufacturer's lifecycle documentation for the LC1F1400ED. Any replacement within the TeSys F range would require verifying the rated operational current (1400 A AC-1), control voltage (48 V DC), and physical footprint — a panel review is necessary before substitution.

MPN
LC1F1400ED