Skip to main content
Schneider Electric LC1F1400W7 — Contactors

Schneider Electric LC1F1400W7 TeSys F Contactor, 1400 A AC-1

MPNLC1F1400W7
Obsolete

Schneider Electric TeSys F contactor, LC1F1400W7, 3-pole, 1400 A AC-1, 265-277 V AC 40-400 Hz coil, plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F1400W7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F1400W7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F1400W7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F1400W7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F1400W7 — Approvals
ParameterValue
StandardsEN 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
LC1F1400W7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

What the 1400 A AC-1 rating means for your load

The LC1F1400W7 is a 3-pole contactor from the TeSys F range rated 1400 A in AC-1 utilisation category — that is the conventional free-air thermal current (Ith) at 40 °C, so it handles resistive loads like large heating banks or furnace elements at that full current without derating. The 265...277 V AC control coil draws 2200 VA inrush and 36 VA hold-in at 50/60 Hz; dropout occurs between 0.3 and 0.5 Uc, so a brownout below about 80 V AC releases the main poles cleanly.

Standards and compliance — what the approvals certify

The contactor is certified to IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1 — the core standards for contactors and motor-starters. Rated insulation voltage is 1000 V per IEC/UL 60947-4-1 and 1500 V per VDE 0110 group C. Impulse withstand voltage is 8 kV, overvoltage category III. Protective treatment is TH (tropicalized) for humid environments.

Mounting and integration — plate-mount, not DIN rail

Mounting is plate-only — no DIN-rail adapter. The footprint is 438 mm wide by 332 mm high by 238.6 mm deep. Power connections use a bar with busbar cross-section up to 100 x 5 mm; control wiring is screw-clamp terminals accepting 1 to 4 mm² flexible or solid. Tightening torque on the power circuit is 58 N.m — a substantial bolted joint, not a spring terminal.

Short-time withstand and breaking capacity — fault handling

Rated short-time withstand current (Icw) is 8000 A for 10 s, 6000 A for 30 s, 4500 A for 1 min, 4000 A for 3 min, and 2600 A for 10 min — all at 40 °C. Rated breaking capacity is 2100 A per IEC 60947-4-1. Associated fuse rating is 1600 A gG at ≤ 440 V. These numbers define the contactor's ability to ride through and interrupt fault conditions without welding or arc damage.

Frequently asked questions

What compliance documentation does LC1F1400W7 carry?

The contactor is certified to IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. Rated insulation voltage is 1000 V (IEC/UL) and 1500 V (VDE 0110 group C). Impulse withstand is 8 kV, overvoltage category III.

MPN