Skip to main content
Schneider Electric LC1F1504B7 — Contactors

Schneider Electric LC1F1504B7 TeSys F Contactor, 250 A AC-3,

MPNLC1F1504B7
Obsolete

Schneider Electric TeSys F LC1F1504B7, 4-pole contactor, 250 A rated operational current (AC-3 at ≤440 V), 75 kW motor power at 400 V AC, 24 V AC 40–400 Hz coil, plate mounting, IP2X front face.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F1504B7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load Motor control
LC1F1504B7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 690 V AC 50/60 Hz
Utilisation categoryAC-3 AC-1 AC-4
LC1F1504B7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F1504B7 — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F1504B7 — Approvals
ParameterValue
StandardsEN 60947-4-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1
LC1F1504B7 — Mechanical
ParameterValue
Width163.5 mm
Height170 mm
Depth171 mm

Product details

The LC1F1504B7 is a TeSys F 4-pole contactor from Schneider Electric, rated 250 A in AC-3 duty at ≤440 V — that is the motor-switching current, not the resistive-heater current. For a 400 V three-phase induction motor, it handles 75 kW (AC-3); at 415 V it carries 80 kW, and at 690 V it goes to 100 kW. The coil is 24 V AC, 40–400 Hz, with a pickup range of 0.85–1.1 Uc and dropout between 0.2–0.55 Uc at 55 °C. Closing time is 35 ms, opening 130 ms — fast enough for most motor-start sequences but not for a safety stop without a separate auxiliary contact block. The contactor is certified to IEC 60947-4-1 and IEC 60947-1, plus JIS C8201-4-1. That means the rated breaking capacity of 1200 A and the rated insulation voltage of 1000 V (1500 V per VDE 0110 group C) are verified under the standard's test conditions. Overvoltage category III suits fixed-installation distribution panels.

Mounting is plate-mount (not DIN rail). Dimensions: 170 mm height, 163.5 mm width, 171 mm depth. The power circuit uses bolted connections or bar connections (25 x 3 mm busbar); control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid wire. Tightening torque: 18 N·m on the power side, 1.2 N·m on the control side. The front face achieves IP2X with shrouds per IEC 60529 and VDE 0106 — basic finger protection, not washdown-rated.

Environmental and durability

Altitude rating is 3000 m without derating. Heat dissipation runs 5.9–7.2 W total; power dissipation per pole is 22 W in AC-1 and 8 W in AC-3. The coil hold-in consumption is 6.6–8.1 VA at 20 °C. Protective treatment is TH (tropicalized).

Frequently asked questions

Where can I buy LC1F1504B7?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of LC1F1504B7?

Rated operational current 250 A AC-3 at ≤440 V; motor power 75 kW at 400 V AC (AC-3); coil 24 V AC 40–400 Hz; certified to IEC 60947-4-1.

What compliance documentation is available for LC1F1504B7?

The contactor is certified to IEC 60947-4-1, IEC 60947-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Overvoltage category III. Protective treatment TH (tropicalized).

MPN
LC1F1504B7