Skip to main content
Schneider Electric LC1F2100Q7 — Contactors

Schneider TeSys F LC1F2100Q7 Contactor, 2100 A AC-1, 380 VAC

MPNLC1F2100Q7
Obsolete

Schneider Electric TeSys F LC1F2100Q7, 3-pole contactor, 2100 A AC-1, 380 VAC 40-400 Hz coil, plate mount, 438 x 332 x 238.6 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F2100Q7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F2100Q7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F2100Q7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F2100Q7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F2100Q7 — Approvals
ParameterValue
StandardsEN 60947-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F2100Q7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

The Schneider Electric TeSys F LC1F2100Q7 is a 3-pole contactor rated 2100 A in AC-1 utilisation category, meaning it is sized for heavy resistive loads — heaters, furnaces, large lighting banks — where the current stays near sinusoidal with minimal inrush. The 380 VAC control coil (40-400 Hz) pulls 2200 VA inrush and holds at 36 VA, with drop-out between 0.3 and 0.5 Uc. Plate-mounted, 438 mm wide, 332 mm tall, 238.6 mm deep; power connections are bolted busbar (100 x 5 mm bar, 4 cables).

Do not apply it to motor starting (AC-3) without derating; this contactor is specified for resistive duty. The short-time withstand (Icw) of 10 kA for 10 seconds tells you the fault-withstand capability before the upstream fuse or breaker must clear — the associated fuse recommendation is 2000 A gG at ≤ 440 V. Heat dissipation is 200 W per pole at AC-1 plus 36 W coil hold-in, so panel ventilation or forced cooling is required in a closed enclosure.

The LC1F2100Q7 carries approvals under IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage (Ui) is 1000 V per IEC, 1500 V per VDE 0110 Group C. Impulse withstand (Uimp) is 8 kV, overvoltage category III. Protective treatment is TH (tropicalized). These certifications cover the documentation a quality or compliance team needs for panel acceptance in most global jurisdictions.

Frequently asked questions

What are the key ratings of the LC1F2100Q7?

3-pole, 2100 A AC-1 at ≤ 40 °C, 380 VAC 40-400 Hz control coil, rated insulation voltage 1000 V (IEC), impulse withstand 8 kV, short-time withstand 10 kA for 10 s.

MPN
LC1F2100Q7