Specifications

Identification

LC1F2100R7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F2100R7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1

Contacts & Poles

LC1F2100R7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F2100R7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F2100R7 — Approvals
ParameterValue
StandardsEN 60947-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F2100R7 — Mechanical
ParameterValue
Width438 mm
Height332 mm
Depth238.6 mm

Product details

Heavy resistive-load switching, 2100 A AC-1

The AC-1 rating governs the continuous current the main poles can carry without derating; at 2100 A and 40 °C ambient, the conventional free-air thermal current (Ith) matches the operational current, so no headroom calculation is needed for purely resistive duty. The 440 V AC control coil draws 2200 VA inrush and 36 VA hold-in, with a dropout threshold of 0.3 to 0.5 Uc — useful to know when sizing the control transformer for a panel with multiple contactors. The contactor carries a rated breaking capacity of 3150 A per IEC 60947-4-1 and a short-time withstand current (Icw) of 10 kA for 10 seconds, 7.5 kA for 30 seconds, and 5.5 kA for 1 minute. These figures define the fault-ride-through capability in a coordinated panel: the contactor can hold in through a downstream fault long enough for an upstream fuse or breaker to clear, provided the associated fuse is rated at 2000 A gG at ≤440 V. The 8 kV impulse withstand voltage (Uimp) and 1000 V rated insulation voltage (Ui) confirm suitability for 400 V class systems with overvoltage category III.

Physical integration and mounting

Mounting is plate-only — no DIN-rail option. The footprint measures 438 mm wide by 332 mm high by 238.6 mm deep. Power connections use bolted busbars with a recommended cross-section of 100 x 5 mm, four cables per pole. Control wiring terminates on screw-clamp terminals accepting 1 to 4 mm² flexible or solid conductors. Tightening torque is 58 N·m on the power circuit and 1.2 N·m on the control circuit. The protective treatment (TH classification) indicates the contactor is treated for tropical environments — relevant for installations in high-humidity or corrosive atmospheres.

The LC1F2100R7 is certified to IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. The rated insulation voltage is 1000 V per IEC and UL, with a VDE 0110 group C rating of 1500 V. Heat dissipation is 36 W total, with 200 W per pole in AC-1 duty — this drives enclosure ventilation requirements in a dense panel.

Frequently asked questions

What is the closest alternative to LC1F2100R7?

No official successor order code is recorded. A parametric replacement must match the 2100 A AC-1 rating, 3-pole configuration, 440 V AC coil, and plate-mount footprint. Consult the TeSys F range for current-production equivalents with similar thermal current (Ith) and breaking capacity.

What compliance documentation does Schneider Electric provide for LC1F2100R7?

The contactor carries certifications to IEC 60947-4-1, EN 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC and UL.

Where can I buy LC1F2100R7?

The LC1F2100R7 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.