Skip to main content
Schneider Electric LC1F2600V7 — Contactors

Schneider Electric LC1F2600V7 TeSys F Contactor, 2600 A AC-1

MPNLC1F2600V7
Obsolete

Schneider Electric TeSys F LC1F2600V7, 3-pole contactor, 2600 A AC-1, 400 V AC 50/60 Hz coil, plate mount, IP20 front face.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC1F2600V7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load

Ratings & Performance

LC1F2600V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 1000 V AC 50/60 Hz
Utilisation categoryAC-1

Contacts & Poles

LC1F2600V7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC1F2600V7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH

Approvals

LC1F2600V7 — Approvals
ParameterValue
StandardsEN 60947-4-1 IEC 60947-1 IEC 60947-4-1 EN 60947-1 JIS C8201-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Mechanical

LC1F2600V7 — Mechanical
ParameterValue
Width519 mm
Height382 mm
Depth251 mm

Product details

What the 2600 A AC-1 Rating Means for Your BOM

The LC1F2600V7 is a 3-pole contactor from the TeSys F range, rated for 2600 A in AC-1 utilisation category at <60 °C. That AC-1 rating governs resistive loads — heating elements, furnaces, lighting banks — where the current waveform is nearly sinusoidal and inrush is minimal. For motor duty (AC-3 or AC-4), the contactor must be derated per the manufacturer's curves; the 2600 A figure is not the motor-switching current. The coil is 400 V AC 40...400 Hz, with an inrush of 2500 VA and a hold-in of 45 VA at 20 °C. Per the specification, the control circuit voltage limits are 0.85...1.1 Uc for operation and 0.3...0.5 Uc for drop-out at 55 °C.

Mounting and Integration — Plate-Mount, Not DIN Rail

Mounting support is plate, not DIN rail. The contactor measures 519 mm wide, 382 mm high, and 251 mm deep. Power circuit connections use bar terminals accepting up to three cables per pole with a busbar cross-section of 100 x 10 mm. Control circuit connections are screw clamp terminals accepting 1...4 mm² flexible or solid cable. Tightening torque is 58 N.m on the power circuit and 1.2 N.m on the control circuit. The IP20 front face with shrouds (per IEC 60529 and VDE 0106) provides basic finger protection but is not rated for washdown environments.

Electrical Performance and Protection Coordination

Rated insulation voltage is 1000 V per IEC 60947-4-1 and UL 60947-4-1. Rated impulse withstand voltage is 8 kV, overvoltage category III. The rated breaking capacity is 3900 A per IEC 60947-4-1. Short-time withstand current (Icw) is 12,000 A for 10 s, 9000 A for 30 s, 7000 A for 1 min, 6000 A for 3 min, and 4000 A for 10 min at 40 °C. The associated fuse rating is 2500 A gG at ≤440 V. Operating time is 40...80 ms closing and 100...200 ms opening. Maximum operating rate is 600 cycles per hour at 55 °C. Heat dissipation is 40 W total, with 250 W per pole in AC-1 duty. The contactor is compliant with EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1.

Frequently asked questions

How do I get current pricing and availability for LC1F2600V7?

Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront for a current quotation; the part is sourced through independent distribution channels.

What compliance documentation does Schneider Electric provide for LC1F2600V7?

The contactor is compliant with EN 60947-4-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1. The protective treatment is TH (tropicalised).

What are the key ratings of LC1F2600V7?

Rated operational current is 2600 A AC-1 at <60 °C. Rated operational voltage is ≤1000 V AC 50/60 Hz. Control circuit voltage is 400 V AC 40...400 Hz. Rated breaking capacity is 3900 A per IEC 60947-4-1.

MPN