Skip to main content
Schneider Electric LC1F2654X7 — Contactors

Schneider LC1F2654X7 TeSys F Contactor, 350 A AC-1, 4P, EOL

MPNLC1F2654X7
Obsolete

Schneider Electric TeSys F LC1F2654X7, 4-pole contactor, 350 A AC-1 at ≤440 V, AC control 550-600 V, end-of-life phase.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F2654X7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F2654X7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F2654X7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F2654X7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
LC1F2654X7 — Approvals
ParameterValue
StandardsIEC 60947-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1
LC1F2654X7 — Mechanical
ParameterValue
Width9.6 in (244.5 mm)
Height8.0 in (203 mm)
Depth8.4 in (213 mm)

Product details

What the 350 A AC-1 rating means for fit

The LC1F2654X7 is a 4-pole (4 NO) contactor from the TeSys F range, rated 350 A at ≤440 V in utilisation category AC-1 — that is the resistive-load curve, not motor starting. The AC-1 rating governs continuous current through resistive heaters, lighting banks, or transformer primaries where inrush is low. For motor duty (AC-3), this contactor is not the right pick; the 350 A figure applies only to the AC-1 band per IEC 60947-4-1. Power dissipation runs 37 W per pole in AC-1 service, with total heat rejection of 8 W from the coil at hold-in. The control circuit is AC 550-600 V at 40-400 Hz, with an inrush of 650 VA dropping to 10 VA sealed.

Mounting and integration constraints

Mounts to a plate — no DIN-rail clip on this frame. Dimensions are 8.4 in deep by 9.6 in wide by 8.0 in high (213 x 244.5 x 203 mm). Power connections are bolted bar (32 x 4 mm) or lug-ring terminals accepting up to 240 mm² cable. Control wiring uses screw-clamp terminals sized for 1-4 mm² flexible or solid. Tightening torque: 1.2 N·m on the control circuit, 35 N·m on the power circuit. Operating altitude is 3000 m without derating; storage temperature range -60 to 80 °C.

Protection coordination and ratings

Associated fuse rating is 315 A aM or 400 A gG at ≤440 V. Rated breaking capacity is 2120 A per IEC 60947-4-1. Insulation voltage is 1000 V per IEC 60947-4-1, 1500 V per VDE 0110 group C. Overvoltage category III. Mechanical durability is 10 million cycles; maximum operating rate is 2400 cycles per hour at 55 °C. Operating time: 40-65 ms closing, 100-170 ms opening. Protective treatment is TH (tropicalised) for humid environments.

Frequently asked questions

What are the key specifications of LC1F2654X7?

Rated operational current 350 A at ≤440 V AC in utilisation category AC-1 (resistive load). Four normally open poles. Control circuit voltage 550-600 V AC at 40-400 Hz. Rated insulation voltage 1000 V per IEC 60947-4-1. Mechanical durability 10 million cycles. Dimensions 8.4 x 9.6 x 8.0 in (213 x 244.5 x 203 mm).

MPN
LC1F2654X7