Skip to main content
Schneider Electric LC1F4004FE7 — Contactors

Schneider TeSys F LC1F4004FE7 Contactor, 500A AC-1, 115VAC C

MPNLC1F4004FE7
Obsolete

Schneider Electric TeSys F LC1F4004FE7, 4-pole contactor, 500 A AC-1 at ≤440 V, 115 V AC 40-400 Hz coil, plate mount, IP20 front face.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F4004FE7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F4004FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F4004FE7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F4004FE7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F4004FE7 — Approvals
ParameterValue
StandardsJIS C8201-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1 IEC 60947-1
LC1F4004FE7 — Mechanical
ParameterValue
Width261 mm
Height206 mm
Depth219 mm

Product details

The Schneider TeSys F LC1F4004FE7 is a 4-pole contactor rated 500 A in AC-1 utilisation category at ≤440 V, making it a fit for resistive heating loads, lighting banks, and non-inductive switching where the current curve stays steady. The 115 V AC coil (40-400 Hz) draws 1075 VA inrush, then holds at 15 VA — the drop-out threshold sits between 0.3 and 0.5 Uc, so a brownout below about 57 V will release the armature cleanly.

The 500 A AC-1 rating governs resistive loads — heaters, furnaces, lamp banks. For motor duty (AC-3), the contactor would derate significantly; the datasheet does not list an AC-3 figure, so if the load is a motor, this is the wrong utilisation category. The 4 NO poles are all normally-open; there are no NC auxiliary contacts built in, so a separate control relay or auxiliary contact block is needed for a holding circuit.

Plate-mounted, not DIN-rail — the 261 mm width and 219 mm depth require a drilled backplate or sub-panel. Power connections use bar (30 x 5 mm busbar) or ring-lug terminals up to 150 mm² cable; control wiring is screw-clamp, 1 to 4 mm² flexible or solid. Tightening torque for the power circuit is 35 N.m — a torque wrench is expected. The 14 W heat dissipation at rated current needs ventilation clearance in the enclosure; stacking multiple units without spacing will raise internal temperature above the 55 °C operating limit.

Designed and tested to IEC 60947-4-1 and EN 60947-4-1, the contactor carries a rated insulation voltage of 1000 V (IEC) and an impulse withstand of 8 kV. The protective treatment (TH) indicates tropicalisation — the coil and magnetic circuit are treated against humidity and corrosion, which matters for unheated warehouses or coastal plants.

Frequently asked questions

What compliance documentation does Schneider provide for the LC1F4004FE7?

The contactor is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. The rated insulation voltage is 1000 V per IEC 60947-4-1, with an 8 kV impulse withstand. The IP20 front face conforms to IEC 60529 and VDE 0106.

MPN
LC1F4004FE7