Schneider LC1F400VD TeSys F Contactor, 400 VDC Coil, 500 A A

MPNLC1F400VD
Obsolete

Schneider Electric TeSys F contactor, LC1F400VD, 3-pole, 400 VDC coil, 500 A AC-3 rated, 200 kW at 400 V AC-3, plate mount, EOL hot.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F400VD — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load Motor control
LC1F400VD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1 AC-4 AC-3
LC1F400VD — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F400VD — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F400VD — Approvals
ParameterValue
StandardsJIS C8201-4-1 EN 60947-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1
LC1F400VD — Mechanical
ParameterValue
Width213 mm
Height206 mm
Depth219 mm

Product details

The Schneider Electric LC1F400VD is a TeSys F three-pole contactor with a 400 VDC coil, rated for motor and resistive loads across AC-1, AC-3, and AC-4 utilisation categories. It switches up to 500 A in AC-3 duty at 440 V, translating to 200 kW at 400 V or 220 kW at 415 V — a heavy-duty machine-tool or pump contactor for a 200 kW class motor. The 400 VDC coil is uncommon; most TeSys F contactors run AC or lower DC coils, so verify your control voltage matches before committing the BOM line.

This part carries an EOL hot lifecycle marker. The manufacturer has flagged end-of-life but the part is still in the supply chain for last-time buys.

The 500 A AC-3 rating (at 440 V, 55 °C) is the headline number for motor switching — it governs the contactor's ability to make and break locked-rotor current. The AC-4 rating (75 kW at 400 V) matters if you need to reverse or plug the motor in-cycle, where the contactor must interrupt full-load current repeatedly.

Plate-mount only — no DIN-rail clip on this frame size. The power circuit uses bolted connections or ring lugs (up to 150 mm² cable or 30 x 5 mm busbar). Control circuit terminals are screw clamp, accepting 1 to 4 mm² flexible or solid. Tightening torque for the power circuit is 35 N.m — substantial, so a torque wrench is expected. IP20 with shrouds on the front face, so it needs a panel or enclosure to meet touch-safe requirements.

Certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, overvoltage category III. The 400 VDC coil has operational limits of 0.85 to 1.1 Uc and drop-out at 0.2 to 0.35 Uc — ensure your DC supply stays within that window, especially under brownout conditions.

Frequently asked questions

What is LC1F400VD's listed depth?

The depth is 219 mm.

What compliance documentation does this brand provide for LC1F400VD?

The part is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. The evidence does not list RoHS or REACH declarations specifically, but Schneider Electric typically provides these on request for TeSys products. Contact us with your RFQ for documentation.