Skip to main content
Schneider Electric LC1F500UD — Contactors

Schneider Electric LC1F500UD TeSys F Contactor, 700 A AC-3,

MPNLC1F500UD
Obsolete

Schneider Electric TeSys F contactor, LC1F500UD, 3-pole, DC standard control circuit, 700 A AC-3 rated operational current, 250 V DC coil, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F500UD — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC1F500UD — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-3 AC-1
LC1F500UD — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F500UD — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
LC1F500UD — Approvals
ParameterValue
StandardsJIS C8201-4-1 IEC 60947-4-1 EN 60947-1 IEC 60947-1 EN 60947-4-1
LC1F500UD — Mechanical
ParameterValue
Width9.2 in (233 mm)
Height9.4 in (238 mm)
Depth9.1 in (232 mm)

Product details

Its headline rating is 700 A at <= 440 V AC in utilisation category AC-3 — that is the current it can make and break under the inductive load of a squirrel-cage motor during starting and running. For a 380-400 V supply, that translates to a motor power rating of 250 kW; at 415 V it covers 280 kW, and at 500 V it reaches 355 kW. The AC-1 rating (resistive load) is not separately stated but the power dissipation per pole at AC-1 is 88 W versus 45 W in AC-3, indicating the thermal headroom for continuous resistive duty. The control circuit is DC standard, with a rated control voltage of 250 V DC. Hold-in power consumption is 6 W at 20 °C; inrush power is 1100 W at the same temperature. The coil operates between 0.85 and 1.1 Uc at 55 °C and drops out between 0.2 and 0.35 Uc — important for verifying that the control supply can deliver the inrush peak without dropping below the dropout threshold. Rated insulation voltage is 1000 V per IEC 60947-4-1, with a higher 1500 V rating per VDE 0110 Group C. The rated breaking capacity is 4000 A conforming to IEC 60947-4-1, which defines the maximum fault current the contactor can safely interrupt. Overvoltage category III means it is suitable for fixed installation in the panel, not for downstream socket-outlet circuits.

This contactor is designed for plate mounting — no DIN-rail clip. The power circuit uses bar connections (2 x 40 x 5 mm) or ring terminals up to 240 mm². Control circuit connections are screw-clamp terminals accepting 1 to 4 mm² flexible or solid wire. Tightening torque for the power circuit is 35 N·m; control circuit is 1.2 N·m.

Standards and environmental

The LC1F500UD is certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Protective treatment is TH (tropicalised) for humid environments. Storage temperature range is -60 to 80 °C.

Frequently asked questions

Where can I buy LC1F500UD and get a price?

The LC1F500UD is sourced through independent distribution channels. Submit an RFQ against this order code; availability and current pricing are confirmed at quote time. No stock or price figures are published for this end-of-life part.

What are the key ratings for LC1F500UD?

The LC1F500UD is a 3-pole contactor rated 700 A AC-3 at <= 440 V, with a 250 V DC coil. Motor power ranges from 147 kW at 220-230 V to 355 kW at 500 V. Rated breaking capacity is 4000 A per IEC 60947-4-1. Mechanical durability is 10 million cycles.

What standards does LC1F500UD comply with?

The LC1F500UD complies with IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 Group C. Protective treatment is TH for tropical environments.

MPN