Skip to main content
Schneider Electric LC1F6309 — Contactors

Schneider Electric LC1F6309 TeSys F Contactor Body, 1000 A A

MPNLC1F6309
Obsolete

Schneider Electric TeSys F series, LC1F6309 contactor body, 3P NO, AC-1 rated 1000 A at 40°C, without coil, plate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F6309 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F6309 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F6309 — Contacts & Poles
ParameterValue
Pole configuration3P
LC1F6309 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Operating altitude9842.52 ft (3000 m) without derating
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open6 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Protective treatment / pollution degreeTH
LC1F6309 — Approvals
ParameterValue
StandardsEN 60947-4-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-1 IEC 60947-1
LC1F6309 — Mechanical
ParameterValue
Width12.2 in (309 mm)
Height12.0 in (304 mm)
Depth10.04 in (255 mm)

Product details

It carries a conventional free-air thermal current (Ith) of 1000 A at 40°C, and its rated operational current (Ie) in AC-1 duty is also 1000 A at 40°C, up to 440 V AC. This is the contactor body only — no coil is included, so you pair it with a separate coil (e.g., the LX1F series) to match your control voltage.

For motor duty (AC-3), the rating will be lower; check the derating curve. The rated insulation voltage (Ui) is 1000 V per IEC 60947-4-1, and the rated impulse withstand voltage (Uimp) is 8 kV, so it's comfortable in 480 V and 600 V panels with adequate clearance. The rated short-time withstand current (Icw) is 5050 A for 10 seconds, which supports coordination with upstream fuses or breakers in a selective scheme.

Mounting is plate-based — no DIN rail clip on this frame size. The power circuit uses bar connections (2 x 60 x 5 mm), and the tightening torque for the power terminals is 58 N.m (513.3 lbf.in). The front face achieves IP20 with shrouds fitted, which is standard for enclosed panel installation. Dimensions: 12.2 in wide, 12.0 in high, 10.04 in deep — plan your gland plate and busbar clearance accordingly.

The contactor is designed and certified to IEC 60947-4-1, EN 60947-4-1, and JIS C8201-4-1, plus the general standard IEC 60947-1. Overvoltage category III and protective treatment TH (tropicalisation) are standard.

Frequently asked questions

Where can I buy LC1F6309 and how do I get a price?

The LC1F6309 is sourced to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time.

What is LC1F6309's listed depth?

The depth is 10.04 in (255 mm).

What is LC1F6309's listed range?

It belongs to the TeSys F range.

What compliance documentation does Schneider provide for LC1F6309?

The contactor is certified to IEC 60947-4-1, EN 60947-4-1, JIS C8201-4-1, and IEC 60947-1. It carries overvoltage category III and protective treatment TH. Specific RoHS/REACH/UL declarations should be confirmed at quote time.

MPN