Skip to main content
Schneider Electric LC1F7804FE7 — Contactors

Schneider LC1F7804FE7 TeSys F Contactor, 1600 A AC-1, 115 V

MPNLC1F7804FE7
Obsolete

Schneider Electric TeSys F, LC1F7804FE7, 4-pole contactor, 1600 A AC-1, 115 V AC 40-400 Hz coil, plate mount, 862 x 434 x 255 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F7804FE7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F7804FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F7804FE7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F7804FE7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F7804FE7 — Approvals
ParameterValue
StandardsEN 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1 IEC 60947-1
LC1F7804FE7 — Mechanical
ParameterValue
Width862 mm
Height434 mm
Depth255 mm

Product details

The LC1F7804FE7: The 1600 A AC-1 rating governs the continuous current-carrying capacity for resistive loads at ≤440 V AC. The 4 NO power poles are all normally-open; for applications needing NC poles or auxiliary contacts, those must be added externally. Control voltage limits are 0.85–1.1 Uc for pickup and 0.2–0.4 Uc for dropout at 55 °C — the coil will hold in down to about 98 V AC and drop out below about 46 V AC. Plate mounting is required; this is not a DIN-rail part. The 862 mm width and 434 mm height mean the panel cutout and enclosure depth must accommodate the full 255 mm depth plus wiring clearance for the 100 x 5 mm busbar connections.

The contactor is designed and tested to IEC 60947-4-1 and EN 60947-4-1, the standards for contactors and motor-starters. It also carries JIS C8201-4-1 compliance. Rated insulation voltage is 1000 V per IEC 60947-4-1 and 1500 V per VDE 0110 group C. Impulse withstand voltage is 8 kV, overvoltage category III. The front face achieves IP20 with shrouds fitted, per IEC 60529 and VDE 0106.

Physical Integration

Plate-mount only. Power circuit connections use bars with a 100 x 5 mm busbar cross-section; tightening torque is 58 N.m. Control circuit wiring uses screw-clamp terminals accepting 1–4 mm² flexible or solid (1 or 2 cables), torqued to 1.2 N.m. Ambient operating range is -5 to 55 °C; storage range is -60 to 80 °C. Protective treatment is TH for tropical environments.

Frequently asked questions

What is the closest alternative to LC1F7804FE7 in the TeSys F family?

No official successor order code is documented for this specific variant. Within the TeSys F range, a functionally similar contactor would need to match the 1600 A AC-1 rating, 4 NO pole configuration, 115 V AC coil, and plate-mount form factor. Any substitution requires verifying the exact BOM requirements and should be confirmed against the customer's approved manufacturer list (AML).

Where can I buy LC1F7804FE7 and get current pricing?

This part is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time commitment.

MPN
LC1F7804FE7